11.2 A: Initialization Parameters
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
569
11.2 A: Initialization Parameters
A parameters [Initialization Parameters]
set the operating environment and operating conditions for the drive.
◆
A1: Initialization
A1 parameters
set the operating environment and operating conditions for the drive. For example, these
parameters set the keypad language, the control method, and the parameter access level for the drive.
■
A1-00: Language Selection
No.
(Hex.)
Name
Description
Default
(Range)
A1-00
(0100)
RUN
Language Selection
Sets the language for the LCD keypad.
0
(0, 1, 7)
Note:
When you initialize the drive with parameter
A1-03 [Initialize Parameters]
, the drive will not reset this parameter.
0 : English
1 : Japanese
7 : Chinese
■
A1-01: Access Level Selection
No.
(Hex.)
Name
Description
Default
(Range)
A1-01
(0101)
RUN
Access Level Selection
Sets user access to parameters. The access level controls the parameters shown on the keypad and
which parameters you can set.
2
(0 - 3)
0 : Operation Only
Access to
A1-00, A1-01, A1-04 [Password]
, and the
U Monitors
.
1 : User Parameters
Access to
A1-00, A1-01, A1-04
, and
A2-01 to A2-32 [User Parameters 1 to 32]
only.
2 : Advanced Level
Access to all parameters, but not Expert Mode parameters.
3 : Expert Level
Access to all parameters including Expert Mode parameters.
This table lists the access permissions to keypad screen in accordance with the setting value of
A1-01
.
Mode
Keypad Screen
A1-01 [Access Level Selection]
Setting
0
1
2
3
Drive Mode
Monitors
Yes
Yes
Yes
Yes
Programming Mode
Parameters
Yes
Yes
Yes
Yes
User Custom Parameters
No
Yes
Yes
Yes
Parameter Backup/Restore
No
No
Yes
Yes
Modified Parameters/Fault
Log
No
No
Yes
Yes
Auto-Tuning
No
No
Yes
Yes
Initial Setup Screen
No
No
Yes
Yes
Diagnostic Tools
No
No
Yes
Yes
Note these points about the Parameter Access.
•
When you use
A1-04
and
A1-05 [Password Setting]
to set a password, you cannot change the values set in
A1-
01 to A1-03, A1-06
, and
A2-01 to A2-32
.
•
When
H1-xx = 1B [MFDI Function Selection = Programming Lockout]
, even if
A1-01 = 1, 2, 3
, you cannot
change parameter settings unless the terminal set to
1B
is turned ON.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...