272
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
Model
EMC Noise Filter Model
Quantity
Manufacturer
4453A
FS5972-600-99
1
Schaffner
4605A
FS5972-410-99
2
Schaffner
■
DC Reactor
Install the DC reactor listed in
for drive models 2003, 2005, 4002, 4003 to comply with IEC/EN
61000-3-2.
Table 4.13 DC Reactors for Harmonic Suppression
Drive Model
DC Reactor
Manufacturer: Yaskawa Electric Corporation
Model
Rating
2003
UZDA-B
5.4 A, 8 mH
2005
UZDA-B
5.4 A, 8 mH
4002
UZDA-B
3.2 A, 28 mH
4003
UZDA-B
3.2 A, 28 mH