YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
259
Model
Terminal
Recomm. Gauge
mm
2
Applicable Gauge
(IP20 Applicable
Gauge
)
mm
2
Wire Stripping
Length
mm
Terminal Screw
Tightening
Torque
N
∙
m (lbf
∙
in)
Size
Shape
4453
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
120 × 4P
70 - 150 × 4P
(150 × 4P)
-
M12
Hex self-locking nut
35
(310)
U/T1, V/T2, W/T3
95 × 4P
70 - 150 × 4P
(120 - 150 × 4P)
-
M12
Hex self-locking nut
35
(310)
-, +1
95 × 4P
95 - 185 × 4P
(185 × 4P)
-
M12
Hex self-locking nut
35
(310)
+3
70 × 4P
35 - 95 × 4P
(95 × 4P)
-
M12
Hex self-locking nut
35
(310)
95 × 2P
60 - 150
(-)
-
M12
Hex bolt (slotted)
32 - 40
(283 - 354)
4605
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
120 × 4P
70 - 150 × 4P
(150 × 4P)
-
M12
Hex self-locking nut
35
(310)
U/T1, V/T2, W/T3
95 × 4P
70 - 150 × 4P
(120 - 150 × 4P)
-
M12
Hex self-locking nut
35
(310)
-, +1
95 × 4P
95 - 185 × 4P
(185 × 4P)
-
M12
Hex self-locking nut
35
(310)
+3
70 × 4P
35 - 95 × 4P
(95 × 4P)
-
M12
Hex self-locking nut
35
(310)
95 × 2P
60 - 150
(-)
-
M12
Hex bolt (slotted)
32 - 40
(283 - 354)
*1
For IP20 protection, use wires that are in the range of applicable gauges.
*2
Remove insulation from the ends of wires to expose the length of wire shown.
*3
For wire gauges more than 30 mm
2
, tighten to a tightening torque of 4.1 N∙m to 4.5 N∙m (36 lbf∙in to 40 lbf∙in).
*4
Install an ELCB with this wire gauge to maintain compliance with IEC/EN 61800-5-1:2007.
*5
Terminals - and +1 have two screws. The Recommended Gauge is the wire gauge for one terminal.
*6
A junction terminal is necessary to connect a braking resistor unit (LKEB-series) to terminals B1 and B2.
■
Connect a Fuse to the Input Side (Primary Side)
The drive circuit protection must comply with IEC/EN 61800-5-1:2007 for protection against a short circuit in the
internal circuitry. Connect semiconductor fuses on the input side for branch circuit protection.
WARNING!
Electrical Shock Hazard. After the drive blows a fuse or trips an RCM/RCD, do not immediately energize the drive
or operate peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all indicators
are OFF. Then check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the cause of
the problem, contact Yaskawa before you energize the drive or peripheral devices. If you do not fix the problem before you
operate the drive or peripheral devices, it can cause serious injury or death.
Three-Phase 200 V Class
Table 4.4 Factory-Recommended Branch Circuit Protection (200 V Class)
Drive Model
Semiconductor Protection Fuse Rated Current
Manufacturer: EATON/Bussmann
2003
FWH-45B
2005
FWH-45B
2008
FWH-45B
2011
FWH-100B
2014
FWH-100B
2018
FWH-100B
2025
FWH-125B
2033
FWH-150B
2047
FWH-200B
2060
FWH-225A
2075
FWH-225A
FWH-250A
2088
FWH-225A
FWH-250A
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...