3.13 Test Run Checklist
Review this checklist and check each item before you do a test run.
Checked
No.
Description
1
Thoroughly read this manual before you do a test run.
2
Check the
”
Wiring Checklist
”
.
3
Energize the drive.
4
Set the voltage for the power supply in
E1-01 [Input AC Supply Voltage]
.
Check the applicable items as specified by your control method.
Table 3.33 V/f Control [A1-02 = 0] and Closed Loop V/f Control [A1-02 = 1]
Checked
No.
Description
5
Select the best V/f pattern for your application and motor characteristics.
Example: For a motor with a rated frequency of 60 Hz, set
E1-03 = 1 [V/f Pattern Selection = Const Trq, 60Hz base, 60Hz max]
as a standard V/
f pattern.
Table 3.34 Closed Loop V/f Control [A1-02 = 1]
Checked
No.
Description
6
Set
F1-01 [Encoder 1 Pulse Count (PPR)]
correctly and make sure that encoder pulse counting direction is correct.
7
Set
C5-01 [ASR Proportional Gain 1] and C5-02 [ASR Integral Time 1]
.
Table 3.35 Open Loop Vector Control [A1-02 = 2], Closed Loop Vector Control [A1-02 = 3], Advanced Open Loop Vector
Control [A1-02 = 4]
Checked
No.
Description
8
Do Rotational Auto-Tuning.
9
Decouple motor shafts and machines when you do Rotational Auto-Tuning
10
Refer to the information on the motor nameplate and set this data correctly:
•
Motor rated power (kW) to
T1-02
•
Motor rated voltage (V) to
T1-03
•
Motor rated current (A) to
T1-04
•
Motor base frequency (Hz) to
T1-05
•
Number of motor poles:
T1-06
•
Motor base speed (min
-1
) to
T1-07
Table 3.36 Closed Loop Vector Control [A1-02 = 3]
Checked
No.
Description
11
Set
F1-01 [Encoder 1 Pulse Count (PPR)]
and F1-05 [Encoder 1 Rotation Selection].
12
Set
C5-01 [ASR Proportional Gain 1] and C5-02 [ASR Integral Time 1]
.
Check items 5 to 12, then check these items.
Checked
No.
Description
13
The keypad will show
“
Rdy
”
after starting to operate the motor.
14
Make sure that you set
b1-01 [Frequency Reference Selection 1]
and
b1-02 [Run Command Selection 1]
correctly as specified by the input
source of the Run command and frequency reference
Example: To input the frequency reference and Run command from the keypad, set
b1-01 = 0 [Keypad]
or
b1-02 = 0 [Keypad]
.
15
If the motor rotates in the opposite direction during test run, switch two of the motor cables (U/T1, V/T2, W/T3).
16
Set
E2-01 [Motor Rated Current (FLA)] and L1-01 [Motor Overload (oL1) Protection]
correctly for motor thermal protection.
17
When you use terminal A1 for the frequency reference:
•
Voltage input
–
Set
H3-01 = 0, 1 [Terminal A1 Signal Level Select = 0 to 10V (Lower Limit at 0), -10 to +10V (Bipolar Reference)]
.
–
Set
H3-02 = 0 [Terminal A1 Function Selection = Frequency Reference]
.
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...