3.10 Crane Application Setup Procedure
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
213
Type
Operation
Motoring
If Light-load Acceleration 2 is enabled, when the frequency reference exceeds
S4-08
, the acceleration times =
S4-17 × C1-01, C1-03, C1-05,
C1-07 [Acceleration Times]
, and the drive will monitor output power.
If the output power ≥
S4-09
then the drive will make acceleration even more gradual, and start the counter for the limit timer set in
S4-13
.
The drive will stop accelerating the motor if any of the following conditions arise, regardless of how much it has smoothed out acceleration
already.
•
Output power reached the level set in
S4-10
.
•
The counter for Light-load Acceleration 2 reaches the value set for the limit timer in
S4-13
.
If the counter reaches the value set for the limit timer in
S4-13
and acceleration is stopped, then the drive will not accelerate again until after
the motor has stopped.
Regenerative operation
If Light-load Acceleration 2 is enabled, then once the frequency reference exceeds
S4-08
, the acceleration times =
S4-17 × C1-01, C1-03, C1-
05, C1-07
, and the drive will monitor output power.
If the output power ≥
S4-11
then the drive will make acceleration even more gradual, and start the counter for the limit timer set in
S4-13
.
The drive will stop accelerating the motor if any of the following conditions arise, regardless of how much it has smoothed out acceleration
already.
•
Output power reached the level set in
S4-12
.
•
The counter for Light-load Acceleration 2 reaches the value set for the limit timer in
S4-13
.
If the counter reaches the value set for the limit timer in
S4-13
and acceleration is stopped, then the drive will not accelerate again until after
the motor has stopped.
Note:
•
The counter for the limit timer will be cleared once the output power falls below
S4-09
.
•
Set
S4-18 = 1 [L-L 2 Select during Regeneration = Enabled]
to enable operation during regeneration.
•
The following fault detection will occur if the output frequency >
S4-08
. The drive detects
oL6 [Light-load Accel 2 Fault (oL6)]
if the
output power is equal to or greater than the fault level set in
S4-15
for the time set in
S4-16
or longer. After the fault detection, the drive
follows the protective operation set in
S4-14
.
S4-14 Setting
Operation after Detection
Mode
0
Ramp to stop
Fault (triggers a fault relay output)
1
Coast to stop
2
Emergency stop
3
Acceleration prohibited
Minor fault
4
Frequency deceleration
Decreases the output frequency only by the frequency set in
S4-21
. This
operation will repeat at the interval set by
S4-16
for as long as the output
power ≥
S4-15
.
-
*1
The keypad will display
oL6
until the fault is reset.
*2
The keypad will flash
oL6
until the Run command is switched OFF, and the motor stops. The keypad will continue to flash
oL6
even
if you perform a fault reset.
◆
Overload Detection
This function limits drive operation depending on how high the drive torque reference or the output current is in
order to ensure safety. If the drive detects an overload situation, then it displays
oL5 [Overload Detection (oL5)]
on the keypad. You can set 2 levels for overload detection, and 2 types of action to take after detecting overtorque.
Note:
1. The overload detection function is enabled only when the brake is released.
2. The overload detection function is disabled when the Run command source is set to the keypad.
■
Related Parameters
Table 3.20 Overload Detection Parameters
No.
Name
Description
S5-01
OverL Detect Operation Select 1
Enables overload detection, and sets the conditions for detection as well as the operation to
perform after an overload situation is detected.
S5-04
OverL Detect Operation Select 2
S5-02
OverL Detect Operation Select 1
Sets the level to trigger an overload.
•
V/f Control Mode
Sets the amount of current to detect overload as the motor rated current is 100%.
•
OLV Control
Sets the amount of torque to detect overload as the motor rated torque is 100%.
S5-05
Overload Detection Torque 2
S5-03
Overload Detection Time 1
If the motor current and motor torque exceed the value set in
S5-02
for longer than the time set in
this parameter, then an overload will be detected.
S5-06
Overload Detection Time 2
If the motor current and motor torque exceed the value set in
S5-05
for longer than the time set in
this parameter, then an overload will be detected.
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...