3.10 Crane Application Setup Procedure
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
205
S2-01 - Run Cmd Minimum On Time (FWD)
S2-02 - Run Cmd Minimum On Time (REV)
•
Entering the Run command when stopped
If the input time for the Run command is shorter than the settings in
S2-01
or
S2-02
, then the drive will hold the
Run command only for the time set in
S2-01
or
S2-02
.
If the input time for the Run command is longer than the settings in
S2-01
or
S2-02
, then the drive will maintain
the Run command internally only for as long as the Run command is input.
This is the same for all of the drive control methods.
•
Run command Entered during Rump to Stop
The drive will carry out the following operation if a Run command is entered in the same direction as the output
frequency. This is the same for all of the drive control methods.
Conditions for Run
Command
S2-01 = 0, S2-02 = 0
S2-01
≠
0, S2-02
≠
0
Output Frequency > f
α
Output Frequency
≤
f
α
Output Frequency > f
α
Output Frequency
≤
f
α
Drive operation
Starts accelerating again.
Closes the brake, and briefly stops. (Stops for at least 50 ms)
The drive will operate the following if a Run command is entered in the direction opposite to the output
frequency.
Conditions for Run
Command
Control Method
S2-01 = 0, S2-02 = 0
S2-01
≠
0, S2-02
≠
0
Output Frequency > f
α
Output Frequency
≤
f
α
Output Frequency > f
α
Output Frequency
≤
f
α
Drive operation
Closed Loop Vector
Control
Switches between Forward/
Reverse run without
engaging the brake.
Closes the brake, and briefly stops. (Stops for at least 50 ms)
Other than CLV control
Closes the brake, and briefly stops. (Stops for at least 50 ms)
*1 For fα, the drive displays whichever value is larger,
S1-01 [Brake Release Frequency(FWD)]
and
S1-02
[Brake Release Frequency(REV)]
, or
S1-12 [Brake Hold Frequency (FWD)]
and
S1-13 [Brake Hold
Frequency (REV)].
*2 The drive will switch between FWD/REV without engaging the brake if a Run command is entered in the
opposite direction while decelerating with the output frequency > fα.
■
Run Command Delay Timer (REV/FWD)
If hoisting the load immediately after lowering it in Open Loop Vector or in V/f Control, then this can cause an
excess amount of current to flow when starting to hoist the load. In such cases, having a small delay before
entering the Run command to hoist makes it possible to lower the peak output current of the drive.
Related Parameters
No.
Name
Adjustment Method
S2-03
Run Cmd Delay Timer (REV/FWD)
Usually, set
S2-03 = 0.0 s
.
*1
This parameter is enabled when
A1-02 = 0, 1, or 2 [Control Method Selection = V/f Control, V/f Control with Encoder, or Open Loop
Vector]
.
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...