Figure 9.30 Location of DIP Switch S4
Terminal
Settings for DIP Switches
Description
A3
AI
(Default)
Functions as multi-function analog input terminal.
Select the function with
H3-06 [Terminal A3 Function Selection]
.
Select the signal level with
H3-05 [Terminal A3 Signal Level Select]
.
•
0: 0 V to 10 V/100% (input impedance: 20 kΩ)
•
1: -10 V to +10 V/-100% to +100% (input impedance: 20 kΩ)
PTC
Functions as PTC input terminal.
Set
H3-06 = E [Motor Temperature (PTC input)]
.
Set
H3-05 = 0 [0 to 10 V]
.
■
Switch ON Termination Resistor for MEMOBUS/Modbus Communications
Set DIP switch S2 to the ON position when the drive is the last slave in a MEMOBUS/Modbus communications.
This drive is equipped with a built-in termination resistor for the RS-485 interface.
Figure 9.31 Location of DIP Switch S2
Table 9.12 MEMOBUS/Modbus Communications Termination Resistor Setting
DIP Switch S2
Description
ON
The built-in termination resistor is switched ON.
OFF (default)
The built-in termination resistor is switched OFF.
10
Drive Start-Up
◆
Setup Wizard
The drive is prepared to run the operation. Use the motor data for Auto-Tuning and test runs.
1.
Energize the drive to show the initial setup screen.
Note:
If the keypad does not show the Initial Setup screen, push
[Menu] to show the Menu screen then push
to
select [Initial Setup].
2.
Select [Set Date/Time] to set the date and time.
Note:
Open the clock battery cover to put in a battery to use the clock functions. Use a Hitachi Maxell “CR2016 Lithium Manganese
Dioxide Lithium Battery” or an equivalent battery with these properties:
• Voltage: 3 V
• Operating temperature range: -20
°
C to +85
°
C (-4
°
F to +185
°
F)
3.
Use
A1-06 [Application Preset]
and
A1-02 [Control Method Selection]
to do Auto-Tuning if necessary.
EN