DIPSWITCH SETTINGS
The dipswitch located on the backside of the NCL Satellite board must be properly set before attempting to
establish serial communications. The following table defines the function of each switch position of DIPSW1:
Switch #
Switch Function
1
Baud Rate - bit 0
2
Baud Rate - bIt 1
3
Operation and Frequency Remote/Local
4
Not Used
5
NCL Drive Subnode Address - bit 0 / MSB
6
NCL Drive Subnode Address - bit 1
7
NCL Drive Subnode Address - bit 2
8
NCL Drive Subnode Address - bit 3
9
NCL Drive Subnode Address - bit 4
10
NCL Drive Subnode Address - bit 5 / LSB
Drive
Satellite DIPSW Position
Subnode
0 = off 1 = on
Address
10
9
8
7
6
5
00
0
0
0
0
0
1
01
0
0
0
0
1
0
02
0
0
0
0
1
1
03
0
0
0
1
0
0
04
0
0
0
1
0
1
05
0
0
0
1
1
0
06
0
0
0
1
1
1
07
0
0
1
0
0
0
08
0
0
1
0
0
1
09
0
0
1
0
1
0
10
0
0
1
0
1
1
11
0
0
1
1
0
0
12
0
0
1
1
0
1
13
0
0
1
1
1
0
14
0
0
1
1
1
1
15
0
1
0
0
0
0
16
0
1
0
0
0
1
17
0
1
0
0
1
0
18
0
1
0
0
1
1
19
0
1
0
1
0
0
20
0
1
0
1
0
1
21
0
1
0
1
1
0
22
0
1
0
1
1
1
23
0
1
1
0
0
0
24
0
1
1
0
0
1
25
0
1
1
0
1
0
26
0
1
1
0
1
1
27
0
1
1
1
0
0
28
0
1
1
1
0
1
29
0
1
1
1
1
0
30
0
1
1
1
1
1
NCL
Satellite DIPSW Position
Baud Rate *
0 = off 1 = on
(Kbaud)
2
1
125
0
0
250
0
1
500
1
0
1
1
*
Must match baud rate setting of NCL Gateway module.
Operation Signal and Satellite DIPSW
Frequency Reference
Position
Source
3
Remote From NCL Network
0
Local From External Terminals
1