Set the Input Signal for the MFAI Terminal A2
Use terminal A2 to input a voltage or a current signal. Set the signal type as shown in
.
Figure 10.20 Location of DIP Switch S1
Table 10.12 MFAI Terminal A2 Signal Settings
Terminal
Input
Signal
DIP Switch Settings
Parameter
Switch
Setting
No.
Signal Level
A2
Current
input
S1
I
(Default)
H3-09
2: 4 mA to 20 mA/0% to 100% (input impedance:
250 Ω)
3: 0 mA to 20 mA/0% to 100% (input impedance:
250 Ω)
Voltage
input
V
0: 0 V to 10 V/0% to 100% (with zero limit) (input
impedance: minimum 15 kΩ)
4: -10 V to +10 V/-100% to 100% (input
impedance: minimum 15 kΩ)
Note:
Use tweezers or a jig with a tip width of approximately 0.8 mm (0.03 in) to set DIP switches.