210
YASKAWA
TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
Table 17.6 Required Short Circuit Protection for GA500 Finless-Type Drive: Three-
Phase 200 V Class
Drive Model
Semiconduc
tor Fuse
Part Number
Manufacturer:
Eaton/
Bussman
Class CC, J or
T Fuse
Maximum
Amps
MCCB
(Schneider
Powerpact
current
limiting MCCB)
Class RK5
Fuse
Maximum
Amps
Enclosure
Volume
Minimum (in
3
)
2001
FWH-25A14F
2
HLL36015
2
600
2002
FWH-25A14F
3.2
HLL36015
3.2
600
2004
FWH-25A14F
6
HLL36015
6
600
2006
FWH-25A14F
10
HLL36015
10
600
2008
FWH-70B
12
HLL36015
12
600
2010
FWH-70B
15
HLL36015
15
600
2012
FWH-70B
20
HLL36020
20
600
2018
FWH-90B
30
HLL36035
30
960
2021
FWH-90B
35
HLL36040
35
960
2030
FWH-100B
50
-
-
960
2042
FWH-150B
70
-
-
960
2056
FWH-200B
90
-
-
2560
2070
FWH-200B
110
-
-
2560
Table 17.7 Required Short Circuit Protection for GA500 Finless-Type Drive: Three-
Phase 400 V Class
Drive Model
Semiconduc
tor Fuse
Part Number
Manufacturer:
Eaton/
Bussman
Class CC, J or
T Fuse
Maximum
Amps
MCCB
(Schneider
Powerpact
current
limiting MCCB)
Class RK5
Fuse
Maximum
Amps
Enclosure
Volume
Minimum (in
3
)
4001
FWH-40B
2
HLL36015
2
960
4002
FWH-40B
3.5
HLL36015
3.5
960
4004
FWH-50B
7
HLL36015
7
960
4005
FWH-70B
9
HLL36015
9
960
4007
FWH-70B
12
HLL36015
12
960