![YASKAWA CIPR-GA50C series Скачать руководство пользователя страница 86](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765086.webp)
86
YASKAWA
SIEPC71061753A GA500 Technical Manual
A - Terminal block (TB2)
B - Terminal block (TB1-1)
C - Terminal block (TB1-2)
D - Terminal block (TB1-3)
Figure 3.35 Control Circuit Terminal Arrangement
■
Control Circuit Wire Gauges and Tightening Torques
Use the tables in this section to select the correct wires. Use shielded wire to wire the control circuit terminal
block. Use crimp ferrules on the wire ends to make the wiring procedure easier and more reliable.
Table 3.12 Control Circuit Wire Gauges and Tightening Torques
Terminal
Block
Terminal
Bare Wire
Crimp Ferrule
Recommended Gauge
mm
2
(AWG)
Applicable Gauge
mm
2
(AWG)
Recommended Gauge
mm
2
(AWG)
Applicable Gauge
mm
2
(AWG)
TB1-1
PS, S1 - S7, SN, SC, SP
0.75
(18)
•
Stranded wire
0.25 - 1.0
(24 - 17)
•
Solid wire
0.25 - 1.5
(24 - 16)
0.5
(20)
0.25 - 0.5
(24 - 20)
TB1-2
AM, AC, A1, A2, +V, H1, H2, HC
TB1-3
MP, RP, AC, D+, D-, P1, C1, P2, C2
TB2
MA, MB, MC
0.75
(18)
•
Stranded wire
0.25 - 1.5
(24 -16)
•
Solid wire
0.25 - 1.5
(24 - 16)
0.5
(20)
0.25 - 1.0
(24 - 17)
Crimp Ferrules
Attach an insulated sleeve when you use crimp ferrules. Refer to
for the recommended external
dimensions and model numbers of crimp ferrules.
Use the CRIMPFOX 6, a crimping tool made by PHOENIX CONTACT.
Figure 3.36 External Dimensions of Crimp Ferrules
Table 3.13 Crimp Ferrule Models and Sizes
Wire Gauge
mm
2
(AWG)
Model
L (mm)
L1 (mm)
φ
d1 (mm)
φ
d2 (mm)
0.25 (24)
AI 0.25-8YE
12.5
8
0.8
2.0
0.34 (22)
AI 0.34-8TQ
12.5
8
0.8
2.0
0.5 (20)
AI 0.5-8WH,
AI 0.5-8OG
14
8
1.1
2.5
◆
Wiring the Control Circuit Terminal
WARNING!
Electrical Shock Hazard. Do not remove covers or touch circuit boards while the drive is energized. If you touch the
internal components of an energized drive, it can cause serious injury or death.
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...