SIEPC71061753A GA500 Technical Manual
75
Model
Terminal
Recommended
Gauge
mm
2
Applicable Gauge
mm
2
Wire
Stripping
Length
mm
Terminal Screw
Tightening Torque
N
∙
m (in
∙
lb)
Size
Shape
4038
R/L1, S/L2, T/L3
14
5.5 - 14
10
M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3
14
3.5 - 14
10
M4
1.5 - 1.7
(13.5 - 15)
-, +1, +2
14
5.5 - 22
18
M5
2.3 - 2.5
(19.8 - 22)
B1, B2
5.5
3.5 - 8
10
M4
1.5 - 1.7
(13.5 - 15)
5.5 - 14
-
M6
5.4 - 6.0
(47.8 - 53.1)
4044
R/L1, S/L2, T/L3
14
5.5 - 22
18
M5
2.3 - 2.5
(19.8 - 22)
U/T1, V/T2, W/T3
14
5.5 - 22
18
M5
2.3 - 2.5
(19.8 - 22)
-, +1, +2
22
5.5 - 30
18
M5
•
≤ 22 mm
2
2.3 - 2.5
(19.8 - 22)
•
30 mm
2
≤
4.1 - 4.5
(36 - 40)
B1, B2
8
2 - 14
10
M4
1.5 - 1.7
(13.5 - 15)
5.5 - 14
-
M6
5.4 - 6.0
(47.8 - 53.1)
4060
R/L1, S/L2, T/L3
22
5.5 - 30
18
M5
•
≤ 22 mm
2
2.3 - 2.5
(19.8 - 22)
•
30 mm
2
≤
4.1 - 4.5
(36 - 40)
U/T1, V/T2, W/T3
14
5.5 - 22
18
M5
2.3 - 2.5
(19.8 - 22)
-, +1, +2
30
8 - 30
18
M5
•
≤ 22 mm
2
2.3 - 2.5
(19.8 - 22)
•
30 mm
2
≤
4.1 - 4.5
(36 - 40)
B1, B2
14
3.5 - 14
10
M4
1.5 - 1.7
(13.5 - 15)
5.5 - 14
-
M6
5.4 - 6.0
(47.8 - 53.1)
*1
Remove insulation from the ends of wires to expose the length of wire shown.
*2
If you turn on the built-in EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp
terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm
2
(copper wire).
•
8-4NS from JST Mfg. Co., Ltd.
•
R8-4S from NICHIFU Co.,Ltd.
◆
Main Circuit Terminal and Motor Wiring
This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and
motor terminals.
WARNING!
Fire Hazard. Do not connect main power supply wiring to drive motor terminals U/T1, V/T2, and W/T3. Connect
main power supply wiring to main circuit input terminals R/L1, S/L2, and T/L3. Incorrect wiring can cause serious injury or death
from fire.
WARNING!
Sudden Movement Hazard. Make sure that you align the phase order for the drive and motor when you connect the
motor to drive output terminals U/T1, V/T2, and W/T3. If the phase order is incorrect, it can cause the motor to run in reverse. If
the motor accidentally runs in reverse, it can cause serious injury or death.
NOTICE:
Do not connect phase-advancing capacitors, LC/RC noise filters, or leakage breakers (RCM/RCD) to the motor
circuit. If you connect these devices to the output circuits, it can cause damage to the drive and connected equipment.
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...