SIEPC71061753A GA500 Technical Manual
677
stop. After you return power, the drive will ramp to stop in the set deceleration time.
L2-29
sets the type of KEB
operation.
Note:
When you set
L2-01
, make sure that you know these items:
•
You can use a Momentary Power Loss Unit on models 2001 to 2042 and 4001 to 4023 for a longer momentary power loss ride through
time. A Momentary Power Loss Unit makes it possible to continue operation of the drive after a maximum of 2 seconds of power loss.
•
When you set
L2-01 = 1 to 4
, keep the magnetic contactor on the drive input side ON and keep the control signal while the drive does
KEB operation.
•
When
L2-01 = 1 to 5
,
Uv [DC Bus Undervoltage]
will flash on the keypad while the drive is attempting to recover from a momentary
power loss. The drive will not output a fault signal at this time.
•
When you use a magnetic contactor between the motor and the drive, keep the magnetic contactor closed while the drive does KEB
operation or tries to restart with Speed Search.
•
Keep the Run command active during KEB operation. The drive cannot accelerate back to the frequency reference when the power
returns.
•
When
L2-01 = 3 to 5
, if the control power supply voltage is less than the CPU operation level during KEB Ride-Thru, it will trigger
Uv1
.
■
L2-02: Power Loss Ride Through Time
No.
(Hex.)
Name
Description
Default
(Range)
L2-02
(0486)
Power Loss Ride Through
Time
Sets the maximum time that the drive will wait until trying to restart after power loss.
Determined by o2-04, C6-
01
(0.0 - 25.5 s)
This function is applicable when
L2-01 = 1, 3 [Power Loss Ride Through Select = Enabled for L2-02 Time,
Kinetic Energy Backup: L2-02]
. If power loss operation is longer than the time set in this parameter, the drive will
detect
Uv1 [DC Bus Undervoltage]
, turn OFF output, and the motor will coast to stop.
Note:
•
The length of time that the drive can recover after a power loss changes when drive capacity changes.
•
The upper limit of the possible momentary power loss Ride-Thru time changes when drive capacity changes.
■
L2-03: Minimum Baseblock Time
No.
(Hex.)
Name
Description
Default
(Range)
L2-03
(0487)
Minimum Baseblock Time
Sets the minimum time to continue the drive output block (baseblock) after a baseblock.
Determined by o2-04, C6-
01
(0.1 - 5.0 s)
Sets the length of time that the drive will wait for the residual voltage in the motor to dissipate in estimation to the
secondary circuit time constant of the motor. If
oC [Overcurrent]
or
ov [DC Bus Overvoltage]
occur at the start of
Speed Search, after power returns, or during DC Injection Braking, increase this setting.
■
L2-04: Powerloss V/f Recovery Ramp Time
No.
(Hex.)
Name
Description
Default
(Range)
L2-04
(0488)
Powerloss V/f Recovery
Ramp Time
Sets the time for the drive output voltage to go back to correct voltage after completing speed
searches.
Determined by o2-04, C6-
01
(0.0 - 5.0 s)
Sets the time for voltage to recover from 0 V to the value set in
E1-05 [Maximum Output Voltage]
.
■
L2-05: Undervoltage Detection Lvl (Uv1)
No.
(Hex.)
Name
Description
Default
(Range)
L2-05
(0489)
Undervoltage Detection Lvl
(Uv1)
Sets the voltage at which a
Uv1 [DC Bus Undervoltage]
fault is triggered or at which the KEB
function is activated. Usually it is not necessary to change this setting.
Determined by o2-04 and
E1-01
(200 V Class: 150 - 210 V,
400 V Class: 300 - 420 V)
NOTICE:
Damage to Equipment. When you set this parameter to a value lower than the default, you must install an AC reactor
on the input side of the power supply. If you do not install an AC reactor, it will cause damage to the drive circuitry.
Note:
If the low voltage detection level is near the lower limit value of
L2-05
, the drive will detect
Uv1
during KEB Ride-Thru operation. Do
not set the value too low when you use the KEB Ride-Thru function.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...