![YASKAWA CIPR-GA50C series Скачать руководство пользователя страница 570](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765570.webp)
570
YASKAWA
SIEPC71061753A GA500 Technical Manual
•
E-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
•
B-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
•
F-type insulation: the resistance value (Ω) shown on the test report at 115 °C × 0.87
■
E4-06: Motor 2 Leakage Inductance
No.
(Hex.)
Name
Description
Default
(Range)
E4-06
(0326)
Motor 2 Leakage
Inductance
Sets the voltage drop from motor 2 leakage inductance as a percentage of Motor Rated Voltage
when motor 2 operates at the rated frequency and rated current.
Determined by o2-04, C6-
01
(0.0 - 60.0%)
The drive sets this parameter during Rotational Auto-Tuning and Stationary Auto-Tuning.
Note:
You cannot usually find the quantity of voltage drop on the motor nameplate. If you do not know the value of the motor 2 leakage
inductance, get the test report from the motor manufacturer.
■
E4-07: Motor 2 Saturation Coefficient 1
No.
(Hex.)
Name
Description
Default
(Range)
E4-07
(0343)
Motor 2 Saturation
Coefficient 1
Sets the motor 2 iron-core saturation coefficient at 50% of the magnetic flux.
0.50
(0.00 - 0.50)
The drive sets this parameter during Rotational Auto-Tuning. The drive uses this value when it operates the motor
in the constant output range.
■
E4-08: Motor 2 Saturation Coefficient 2
No.
(Hex.)
Name
Description
Default
(Range)
E4-08
(0344)
Motor 2 Saturation
Coefficient 2
Sets the motor 2 iron-core saturation coefficient at 75% of the magnetic flux.
0.75
(E4-07 - 0.75)
The drive sets this parameter during Rotational Auto-Tuning. The drive uses this value when it operates the motor
in the constant output range.
■
E4-09: Motor 2 Mechanical Loss
No.
(Hex.)
Name
Description
Default
(Range)
E4-09
(033F)
Expert
Motor 2 Mechanical Loss
Sets the mechanical loss of motor 2. It is set as a percentage of
E4-11 [Motor 2 Rated Power]
.
Usually it is not necessary to change this setting.
0.0%
(0.0 - 10.0%)
Adjust this parameter in these conditions. The drive adds the configured mechanical loss to the torque reference
value as a torque compensation value:
•
There is a large quantity of torque loss from motor bearing friction.
•
There is a large quantity of torque loss in fans and pumps.
■
E4-10: Motor 2 Iron Loss
No.
(Hex.)
Name
Description
Default
(Range)
E4-10
(0340)
Motor 2 Iron Loss
Sets the motor iron loss for motor 2.
Determined by o2-04, C6-
01
(0 - 65535 W)
■
E4-11: Motor 2 Rated Power
No.
(Hex.)
Name
Description
Default
(Range)
E4-11
(0327)
Motor 2 Rated Power
Sets the motor rated power in the units from
o1-58 [Motor Power Unit Selection]
.
Determined by o2-04, C6-
01
(0.00 - 650.00 kW)
Auto-Tuning automatically sets this parameter to the value input for [Motor Rated Power].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...