![YASKAWA CIPR-GA50C series Скачать руководство пользователя страница 518](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765518.webp)
518
YASKAWA
SIEPC71061753A GA500 Technical Manual
■
b8-18: E-Save d-axis Current FilterTime
No.
(Hex.)
Name
Description
Default
(Range)
b8-18
(01FA)
Expert
E-Save d-axis Current
FilterTime
Sets the d-axis current reference filter time constant.
0.100 s
(0.000 - 5.000 s)
■
b8-19: E-Save Search Frequency
No.
(Hex.)
Name
Description
Default
(Range)
b8-19
(0B40)
Expert
E-Save Search Frequency
Sets the frequency of Energy-saving control search operations. Usually it is not necessary to
change this setting.
Determined by A1-02
(10 - 300 Hz)
Note:
•
If low inertia causes vibration in the machine, increase the setting value in 10 Hz increments and check the response. If
A1-02 = 8
[Control Method Selection = EZOLV]
, increase the setting value in 1 Hz increments.
•
To make the motor more efficient, decrease the setting value in 1 Hz increments until the point immediately before machine vibration
starts to occur.
■
b8-20: E-Save Search Width
No.
(Hex.)
Name
Description
Default
(Range)
b8-20
(0B41)
Expert
E-Save Search Width
Sets the amplitude of Energy-saving control search operations.
1.0 degrees
(0.1 - 5.0 degrees)
An increase in the value can make the operational efficiency better. However, if the load inertia is small, it may be
necessary to adjust the value to prevent machine vibration.
Note:
•
If low inertia causes vibration in the machine, decrease the setting value in 1.0-degree increments and check the response.
•
To make the motor more efficient, increase the setting value in 1.0-degreee increments until the point immediately before machine
vibration starts to occur.
■
b8-21: PM E-Save Search Gain
No.
(Hex.)
Name
Description
Default
(Range)
b8-21
(0B42)
Expert
PM E-Save Search Gain
Sets the gain of Energy-saving control search operations.
0.3Hz
(0.1 - 20.0 Hz)
When you decrease the value of
C5-01 [ASR Proportional Gain 1]
, also decrease the value of
b8-21
to keep the
correct ratio.
■
b8-22: PM E-Save Search LPF Cutoff Freq
No.
(Hex.)
Name
Description
Default
(Range)
b8-22
(0B43)
Expert
PM E-Save Search LPF
Cutoff Freq
Sets the frequency of the filter used to extract the high-efficiency phase from search operations.
Usually it is not necessary to change this setting.
10.0 Hz
(1.0 - 30.0 Hz)
■
b8-23: PM E-Save Search Limit
No.
(Hex.)
Name
Description
Default
(Range)
b8-23
(0B44)
Expert
PM E-Save Search Limit
Sets the search operations output limit. Usually it is not necessary to change this setting.
15.0 degrees
(0.0 - 30.0 degrees)
When the motor characteristics are correct, increase this value to make the motor more efficient.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...