SIEPC71061753A GA500 Technical Manual
485
3 : Option PCB
Use a communications option card connected to the drive to enter the Run command.
Refer to the instruction manual included with the option card to install and set the option card.
Note:
If you set
b1-15 = 3
but you do not connect an option card,
oPE03 [Multi-Function Input Setting Err]
will flash on the keypad.
4 : Pulse Train Input
Use a pulse train signal from the pulse train input terminal RP to enter the frequency reference.
Do this procedure to make sure that the pulse train signal is operating correctly.
1. Set
b1-15 = 4
,
H6-01 = 0 [Terminal RP Pulse Train Function = Frequency Reference]
.
2. Set
H6-02 [Terminal RP Frequency Scaling]
to the number of pulses that determine 100% of the frequency
reference.
3. The terminal set in
H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection]
is activated.
4. Enter a pulse train signal on the terminal RP and make sure that the keypad shows a correct frequency
reference.
■
b1-16: Run Command Selection 2
No.
(Hex.)
Name
Description
Default
(Range)
b1-16
(01C5)
Run Command Selection 2
Sets the input method for Run Command 2 when the user switches the control circuit terminals
ON/OFF to change the Run command source.
0
(0 - 3)
Activate
H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection]
to enable this parameter.
0 : Keypad
Use the keypad to enter the Run command.
You can use the JOG operation or the FWD/REV commands from the keypad.
Note:
The
is on while the keypad is the Run command source.
1 : Digital Input
Use the control circuit terminals to enter the Run command. Select the input method for the Run command with
an
H1-xx
parameter.
Set
H1-xx = 0, 40 to 43 [3-Wire Sequence, Run Command (2-Wire Sequence)]
. The default setting is 2-wire
sequence 1.
•
2-wire Sequence 1
This sequence has two input types: FWD/Stop and REV/Stop. Set
A1-03 = 2220 [Initialize Parameters = 2-
Wire Initialization]
to initialize the drive and set terminals S1 and S2 for a 2-wire sequence.
•
2-wire Sequence 2
This sequence has two input types: Run/Stop and FWD/REV.
•
3-Wire Sequence
This sequence has three input types: Run, Stop, and FWD/REV. Set
A1-03 = 3330 [Initialize Parameters = 3-
Wire Initialization]
to initialize the drive and set terminals S1, S2, and S5 for a 3-wire sequence.
2 : Memobus/Modbus Communications
Use MEMOBUS/Modbus communications to enter the Run command.
3 : Option PCB
Use a communications option card or input option card connected to the drive to enter the Run command.
Refer to the instruction manual included with the option card to install and set the option card.
Note:
If
b1-16 = 3
but no option card is connected, then
oPE03 [Multi-Function Input Setting Err]
will flash on the keypad.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...