10.6
Drive Specifications
Note:
•
To get the OLV specifications, do Rotational Auto-Tuning.
•
To get the longest product life, install the drive in an environment that meets the necessary specifications.
Table 10.7 Control Characteristics
Item
Specification
Control Methods
•
V/f Control
•
Open Loop Vector
•
PM Open Loop Vector
•
PM Advanced Open Loop Vector
•
EZ Vector Control
Frequency Control
Range
•
V/f, OLV, and OLV/PM: 0.01 Hz to 590 Hz
•
AOLV/PM: 0.01 Hz to 270 Hz
•
EZOLV: 0.01 Hz to 120 Hz
Frequency Accuracy
(Temperature
Fluctuation)
Digital inputs: ±0.01% of the maximum output frequency (-10 °C to +40 °C (14 °F to 104 °F))
Analog inputs: Within ±0.1% of the maximum output frequency (25 °C ±10 °C (77 °F ±18 °F))
Frequency Setting
Resolution
Digital inputs: 0.01 Hz
Analog inputs: 1/2048 of the maximum output frequency (11-bit signed)
Output Frequency
Resolution
0.001 Hz
Frequency Setting
Signal
Main speed frequency reference: 0 Vdc to 10 Vdc (20 kΩ), 4 mA to 20 mA (250 Ω), 0 mA to 20 mA (250 Ω)
Main speed reference: Pulse train input (maximum 32 kHz)
Starting Torque
•
V/f: 150%/3 Hz
•
OLV: 150%/1 Hz
•
OLV/PM: 100%/5% speed
•
AOLV/PM: 100%/0 min
-1
(when high frequency injection is enabled)
•
EZOLV: 100%/10% speed
Note:
Correctly select the drive and motor capacity for this starting torque in these control methods:
•
OLV
•
AOLV/PM
Speed Control Range
•
V/f: 1:40
•
OLV: 1:100
•
OLV/PM: 1:10
•
AOLV/PM: 1:100 (when high frequency injection is enabled)
•
EZOLV: 1:10
Zero Speed Control
Possible in these control methods:
•
AOLV/PM
Torque Limits
Parameter settings allow different limits in four quadrants in these control methods:
•
OLV
•
AOLV/PM
•
EZOLV
Acceleration and
Deceleration Times
0.0 s to 6000.0 s
The drive can set four pairs of different acceleration and deceleration times.
Braking Torque
Approximately 20%
Approximately 125% with a dynamic braking option
•
Short-time average deceleration torque
Motor output 0.1/0.2 kW: over 150%
Motor output 0.4/0.75 kW: over 100%
Motor output 1.5 kW: over 50%
Motor output 2.2 kW and larger: over 20%, Overexcitation Braking/High Slip Braking allow for approximately 40%
WARNING!
Set L3-04 = 0 [Stall Prevention during Decel = Disabled] when you operate the drive with:
• a regenerative converter
• regenerative unit
• braking resistor
• braking resistor unit.
If you set the parameter incorrectly, the drive can decelerate for too long and cause serious injury or death.
Note:
•
Short-time average deceleration torque refers to the torque needed to decelerate the motor (uncoupled from the load) from the rated speed to zero.
Motor characteristics can change the actual specifications.
•
Motor characteristics change the continuous regenerative torque and short-time average deceleration torque for motors 2.2 kW and larger.
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...