SIEPC71061753A GA500 Technical Manual
4.12
Test Run Checklist
Examine the items in this checklist and check each item before a test run.
Checked
No.
Description
1
Correctly install and wire the drive as specified by this manual.
2
Energize the drive.
3
Set the voltage for the power supply in
E1-01 [Input AC Supply Voltage]
.
Check the applicable items as specified by your control method.
WARNING!
Sudden Movement Hazard. Correctly wire the start/stop and safety circuits before you energize the drive. If you
momentarily close a digital input terminal, it can start a drive that is programmed for 3-Wire control and cause serious injury or
death from moving equipment.
Table 4.22 V/f [A1-02 = 0]
Checked
No.
Description
4
Select the best V/f pattern for your application and motor characteristics.
Example: For a motor with a rated frequency of 60 Hz, set
E1-03 = 1 [V/f Pattern Selection = Const Trq, 60Hz base, 60Hz max]
as a standard V/
f pattern.
Table 4.23 OLV [A1-02 = 2]
Checked
No.
Description
5
Decouple motor shafts and machines.
6
Refer to the information on the motor nameplate and set this data correctly:
•
Motor rated power (kW) to
T1-02
•
Motor rated voltage (V) to
T1-03
•
Motor rated current (A) to
T1-04
•
Motor base frequency (Hz) to
T1-05
•
Number of motor poles to
T1-06
•
Motor base speed (min
-1
) to
T1-07
7
Do Rotational Auto-Tuning.
Table 4.24 OLV/PM [A1-02 = 5]
Checked
No.
Description
8
Set
E5-01 through E5-24 [PM Motor Settings]
.
Table 4.25 AOLV/PM [A1-02 = 6]
Checked
No.
Description
9
Set
E5-01 through E5-24 [PM Motor Settings]
.
10
Set
C5-01 [ASR Proportional Gain 1] and C5-02 [ASR Integral Time 1]
.
Checked
No.
Description
11
Make sure that the keypad shows READY LED before you start to operate the motor.
12
To give the Run command and frequency reference from the keypad, push
to set to LOCAL Mode (when in LOCAL Mode, the LO/RE
LED illuminates).
13
If the motor rotates in the opposite direction during test run, switch two of the motor cables (U/T1, V/T2, W/T3).
14
Set Heavy Duty or Normal Duty Mode with
C6-01 [Normal / Heavy Duty Selection]
to conform to the load condition.
15
Set
E2-01 [Motor Rated Current (FLA)] and L1-01 [Motor Overload (oL1) Protection]
correctly for motor thermal protection.
16
Set the drive for REMOTE Mode when the control circuit terminals supply the Run command and frequency reference (in REMOTE Mode, the
LO/RE LED turns OFF).
17
When you use terminal A1 for the frequency reference:
•
Set
H3-01 = 0, 1 [Terminal A1 Signal Level Select = 0 to 10V (Lower Limit at 0), 0 to 10V (Without Lower Limit)]
.
•
Set
H3-02 = 0 [Terminal A1 Function Selection = Frequency Reference]
.
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...