2 Mechanical & Electrical Installation
YASKAWA ELECTRIC
SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
69
Model
Terminals
Recommen
ded Gauge
mm
2
Applicable
Gauge
(IP20
Applicable
Gauge
)
mm
2
Wire
Stripping
mm
Terminal Screw
Tightening
Torque
N
∙
m (lb.
∙
in.)
Size
Shape
2283
R/L1, S/L2, T/L3
80 × 2P
22 - 100 × 2P
(80 - 100 × 2P)
-
M10
Hex self-
locking nut
20
(177)
U/T1, V/T2, W/T3
80 × 2P
22 - 100 × 2P
(80 - 100 × 2P)
-
M10
Hex self-
locking nut
20
(177)
-, +1
100 × 2P
30 - 125 × 2P
(100 - 125 ×
2P)
-
M10
Hex self-
locking nut
20
(177)
+3
60 × 2P
22 - 60 × 2P
(50 - 60 × 2P)
-
M10
Hex self-
locking nut
20
(177)
38
38 - 200
(-)
-
M10
Hex bolt
(slotted)
18 - 23
(159 - 204)
2346
R/L1, S/L2, T/L3
125 × 2P
60 - 125 × 2P
(125 × 2P)
-
M12
Hex self-
locking nut
35
(310)
U/T1, V/T2, W/T3
125 × 2P
60 - 125 × 2P
(125 × 2P)
-
M12
Hex self-
locking nut
35
(310)
-, +1
150 × 2P
100 - 150 × 2P
(150 × 2P)
-
M12
Hex self-
locking nut
35
(310)
+3
80 × 2P
38 - 150 × 2P
(150 × 2P)
-
M12
Hex self-
locking nut
35
(310)
38
38 - 200
(-)
-
M12
Hex bolt
(slotted)
32 - 40
(283 - 354)
2415
R/L1, S/L2, T/L3
125 × 2P
60 - 125 × 2P
(125 × 2P)
-
M12
Hex self-
locking nut
35
(310)
U/T1, V/T2, W/T3
125 × 2P
60 - 125 × 2P
(125 × 2P)
-
M12
Hex self-
locking nut
35
(310)
-, +1
150 × 2P
100 - 150 × 2P
(150 × 2P)
-
M12
Hex self-
locking nut
35
(310)
+3
80 × 2P
38 - 150 × 2P
(150 × 2P)
-
M12
Hex self-
locking nut
35
(310)
60
60 - 200
(-)
-
M12
Hex bolt
(slotted)
32 - 40
(283 - 354)
*1
For IP20 protection, use wires that are in the range of applicable gauges.
*2
Remove insulation from the ends of wires to expose the length of wire shown.
*3
For wire gauges more than 30 mm
2
, tighten to a tightening torque of 4.1 to 4.5 N∙m (36 to 40 lb.∙in.).
*4
Terminals - and +1 have two screws. The Recommended Gauge is the wire gauge for one terminal.
*5
A junction terminal is necessary to connect a braking resistor unit (LKEB-series) to terminals B1 and B2.