TM.iQp.02 iQpump Drive Programming Manual
P3-02
0615H
Drive Multi/Maximum
Level
Max-Multi Level
Sets the maximum level used for multiplex pumping operation.
Parameter is active when P3-01 = 0 or P3-01 = 2 is selected.
P3-01=0:
When the output frequency rises above the level
programmed in P3-02 for a time specified in P3-04, the next available
pump will be added to the system by means of a multi-function digital
output closure (H2-XX = 40, 41).
P3-01=1:
Not Used.
P3-01=2:
When the output frequency rises above level programmed in
P3-02 and the delta feedback (setpoint minus feedback) has exceeded
the level programmed in P3-03 for a time specified in P3-04, the next
available pump will be added to the system by means of a multi-
function digital output closure (H2-XX = 40, 41).
0.0 to
120.00
59.0 Hz Programming
P3-03
0616H
Add Pump Delta Level
Add Pump D-Lvl
Sets the level used for multiplex pumping operation. The parameter is
active when P3-01 =1 or P3-01 = 2 is selected.
P3-01=0:
Not Used.
P3-01=1:
When the delta feedback (setpoint minus feedback) has
exceeded the level programmed in P3-03 for a time specified in P3-04,
the next available pump will be added to the system by means of a
multi-function digital output closure. (H2-XX = 40, 41).
P3-01=2:
When the output frequency rises above level programmed in
P3-02 and the delta feedback (Setpoint minus feedback) has exceeded
the level programmed in P3-03 for a time specified in P3-04, the next
available pump will be added to the system by means of a multi-
function digital output closure. (H2-XX = 40, 41).
Note:
Do not program this level too close to the system setpoint or
excessive cycling of the pump system may occur.
0.0 to
6000.0
(system
units P1-
02)
0.0
(system
units P1-
02)
Programming
P3-04
0617H
Add Pump Delay Time
Add Pump Dly Tm
Sets the delay time before a pump is added to the system. Works in
conjunction with parameters P3-02, P3-03, and P2-11 to P2-19.
0 to 3600
2 sec
Programming
P3-05
0618H
Shutdown Pump Delta
Level
Shdn Pump D-Lvl
Sets the level used for multiplex pumping operation. Parameter is
active when P3-01 = 1 or P3-01 = 2 is selected.
P3-01=0:
Not Used.
P3-01=1:
When the delta feedback (feedback minus setpoint) has
exceeded the level programmed in P3-05 for a time specified in P3-
06,the last pump that was brought online will be shutdown by means of
a multi-function digital output opening. (H2-XX = 40, 41).
P3-01=2:
When the output frequency drops below level programmed
in P3-09 or P3-10 (depends on last pump running) and the delta
feedback (feedback minus setpoint) has exceeded the level
programmed in P3-05 for a time specified in P3-06, the last pump that
was brought online will be shutdown by means of a multi-function
digital output opening. (H2-XX = 40, 41).
Note:
Do not program this level too close to the system setpoint or
excessive cycling of the pump system may occur.
0.0 to
6000.0
(system
units P1-
02)
0.0
(system
units P1-
02)
Programming
P3-06
0619H
Shutdown Pump Delay
Time
Shdn Pump Dly Tm
Sets the delay time before one of the additional across the line pumps is
shutdown.Works in conjunction with parameters P3-02 and P3-03.
0 to 3600
5 sec
Programming
P3-07
061AH
Multi Pump Setpoint
Increase
MP Setpoint Inc.
Sets the amount the Drive’s setpoint will decrease for each time a new
pump is brought offline.
Pump 1: Setpoint.
Pump 1+2: Se P3-07.
Pump 1+2+3: Se (2 x P3-07).
0.0 to
6000.0
(system
units P1-
02)
0.0
(system
units P1-
02)
Programming
P3-08
061BH
Multi Pump Setpoint
Decrease
MP Setpoint Dec.
Sets the amount the Drive’s setpoint will increase for each time a new
pump is brought online.
Pump 1: Setpoint.
Pump 1+2: Setpoint - P3-08.
Pump 1+2+3: Setpoint - (2 x P3-08).
0.0 to
6000.0
(system
units P1-
02)
0.0
(system
units P1-
02)
Programming
Denotes that parameter can be changed when the Drive is running.
Parameter
No.
Modbus
Address
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Page
No.
Содержание CIMR-P7U-2011-107
Страница 1: ...iQpump Drive Programming Manual Document Number TM iQp 02 ...
Страница 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK ...