1  Safety Instructions and General Warnings

YASKAWA Electric TOEP C710606 27 AC Drive - J1000 Quick Start Guide

 EN5

ENGLI

S

H

‹

Safety Warnings

NOTICE

Indicates a property damage message.

WARNING

Electrical Shock Hazard

• Do not attempt to modify or alter the drive in any way not explained in this manual. 

Failure to comply could result in death or serious injury.
Yaskawa is not responsible for any modification of the product made by the user. This product
must not be modified.

• Do not touch any terminals before the capacitors have fully discharged.

Failure to comply could result in death or serious injury.
Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains
charged even after the power supply is turned off. The charge indicator LED will extinguish
when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least one minute
after all indicators are off and measure the DC bus voltage level to confirm safe level. 

• Do not allow unqualified personnel to use equipment. 

Failure to comply could result in death or serious injury.
Maintenance, inspection, and replacement of parts must be performed only by authorized
personnel familiar with installation, adjustment, and maintenance of AC drives. 

• Do not remove covers or touch circuit boards while the power is on.

Failure to comply could result in death or serious injury. 

• Make sure the protective earthing conductor complies with technical standards and local 

safety regulations.

The leakage current of this drive exceeds 3.5 mA. Therefore, according to IEC 61800-5-1,
automatic power supply interruption in case of discontinuity of the protective earthing
conductor must be provided or a protective earthing conductor with a cross section of at least
10 mm

2

 (Cu) or 16 mm

2

 (Al) must be used.

• Use appropriate equipment for residual current monitoring/detection (RCM/RCD).

This drive can cause a residual current with a DC component in the protective earthing
conductor. Where a residual current operated protective or monitoring device is used for
protection in case of direct or indirect contact, always use an RCM or RCD of type B according
to IEC 60755.

• Always ground the motor-side grounding terminal. 

Improper equipment grounding could result in death or serious injury by contacting the motor
case.

Содержание CIMR-JC

Страница 1: ...put 0 1 to 5 5 kW 200 V Class Single Phase Input 0 1 to 2 2 kW 400 V Class Three Phase Input 0 2 to 5 5 kW MANUAL NO TOEP C710606 27A Type CIMR JC To properly use the product read this manual thorough...

Страница 2: ...EN2 YASKAWA Electric TOEP C710606 27 AC Drive J1000 Quick Start Guide...

Страница 3: ...Start Guide J1000 Quick Start Guide ENGLISH 1 Safety Instructions and General Warnings 2 2 Mechanical Installation 7 3 Electrical Installation 9 4 Keypad Operation 16 5 Start Up 18 6 Parameter Table 2...

Страница 4: ...ded to the end user Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the manual NO OTHER WARRANTY EXPRESS OR IMPLIED...

Страница 5: ...result in death or serious injury Maintenance inspection and replacement of parts must be performed only by authorized personnel familiar with installation adjustment and maintenance of AC drives Do n...

Страница 6: ...could result in death or serious injury by fire Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power Do not use improper combustible materi...

Страница 7: ...t in further damage to the equipment Do not connect or operate any equipment with visible damage or missing parts Install adequate branch circuit short circuit protection per applicable codes Failure...

Страница 8: ...nd overvoltage category 3 in accordance with IEC664 Ground the neutral point of the main power supply for 400 V Class drives Precautions for UL cUL Standards Compliance This drive is tested in accorda...

Страница 9: ...vironment Conditions Installation Area Indoors Ambient Temperature 10 C to 50 C When using an enclosure panel install a cooling fan or air conditioner in the area to ensure that the air temperature in...

Страница 10: ...8 128 118 56 118 5 38 5 109 5 M4 1 0 BA0006 108 128 137 5 96 118 5 58 129 M4 1 7 BA0010 108 128 154 96 118 5 58 145 5 M4 1 8 2A0001 68 128 76 56 118 5 6 5 67 5 M4 0 6 2A0002 68 128 76 56 118 5 6 5 67...

Страница 11: ...uses Main Switch Forward Stop Reverse Stop External Fault Fault Reset Multi speed 1 Multi function digital inputs default setting Link Thermal relay Braking resistor option J1000 Ground Multi function...

Страница 12: ...3 5 BA0002 FS23638 10 07 2 5 M3 5 M3 5 M3 5 BA0003 FS23638 10 07 2 5 M3 5 M3 5 M3 5 BA0006 FS23638 20 07 2 5 M4 M4 M4 BA0010 FS23638 20 07 4 M4 M4 M4 2A0001 FS23637 8 07 2 5 M3 5 M3 5 M3 5 2A0002 FS23...

Страница 13: ...ype Manufacturer Ferraz Fuse Ampere Rating A Fuse Type Manufacturer Bussmann 500 Vac 200 kAIR Fuse Ampere Rating A Single Phase 200 V Class BA0001 A6T6 6 FWH 25A14F 25 BA0002 A6T10 10 FWH 25A14F 25 BA...

Страница 14: ...es smaller than 1 kW for compliance with the EN61000 3 2 Refer to the instruction manual or contact your supplier for details EMC Standards Compliant Wiring of Single and Three Phase Units Terminal Sc...

Страница 15: ...ring the Main Circuit Output Consider the following precautions for the output circuit wiring Do not connect any other load than a 3 phase motor to the drives output Never connect a power source to th...

Страница 16: ...control power supply use a UL Listed Class 2 power supply Use twisted pair or shielded twisted pair cables for control circuits to prevent operating faults Ground the cable shields with the maximum c...

Страница 17: ...Photocoupler inputs 24 Vdc 8 mA Note Drive preset to sinking mode NPN When using source mode set DIP switch S3 to SOURCE and use an external 24 Vdc 10 power supply SC Multi function input common Seque...

Страница 18: ...active during power up Up Arrow Key Scrolls up to select parameter numbers setting values etc Down Arrow Key Scrolls down to select parameter numbers setting values etc STOP Key Stops the drive ENTER...

Страница 19: ...ut Frequency Output Current Output Voltage Monitor Display Verify Menu Setup Mode Parameter Setting Mode DRV LED is on A Run command will start the motor The Monitor Displays are used to read out driv...

Страница 20: ...parameters if necessary Final check the operation and verify the settings Drive is ready to run the application Intstall and wire the drive as explained Turn the power on Initialize the drive if nece...

Страница 21: ...the drive is in the REMOTE mode Mode Heavy Duty Ratings HD Normal Duty Rating ND C6 01 0 1 Application Applications with a constant torque like extruders conveyors and cranes High overload capability...

Страница 22: ...analog input Select the input sig nal level in parameter H3 01 NOTICE If the input signal level of input A1 is switched between voltage and current make sure that DIP switch S1 is in the correct posi...

Страница 23: ...activated in the C2 parameters for softer accel decel start and end Test Run Perform the following steps to start up the machine after all parameter settings have been done 1 Run the motor without loa...

Страница 24: ...ng Current Sets the DC Injection Braking cur rent as a percentage of the drive rated current b2 03 DC Inj Braking Time DC Excitation Time at Start Sets the time of DC Injection Brak ing at start in un...

Страница 25: ...rent Magnetizing current in Ampere E2 05 Motor Line to Line Resistance Sets the phase to phase motor resistance in ohms Digital Input Settings H1 01 to H1 05 DI S1 to S5 Function Selection Selects the...

Страница 26: ...03 Output Current A U1 06 Output Voltage Reference Vac U1 07 DC Bus Voltage Vdc U1 10 Input Terminal Status Par Name Description 1 Digital input 1 terminal S1 enabled 1 Digital input 2 terminal S2 en...

Страница 27: ...e block function is assigned to one of the digital inputs and the input is off The drive does not accept Run commands ControlCircuit Fault There is a problem in the drive s control circuit Cannot Rese...

Страница 28: ...load is too heavy The drive capacity is too small Too much torque at low speed DC Overvoltage DC bus voltage rose too high The deceleration time is too short Stall prevention is disabled Braking chop...

Страница 29: ...ers to the proper values oPE03 A contradictory setting is assigned to multi func tion contact inputs H1 01 through to H1 05 The same function is assigned to two inputs this excludes External fault and...

Страница 30: ...and closed loop connec tors or CSA certified ring connectors sized for the selected wire gauge to maintain proper clearances when wiring the drive Use the correct crimp tool to install connectors per...

Страница 31: ...R5 5 5 2 0 to 2 5 17 7 to 22 1 M6 R5 5 6 4 0 to 5 0 35 4 to 44 3 M8 R5 5 8 9 0 to 11 0 79 7 to 97 4 8 8 M4 8 4 1 2 to 1 5 10 6 to 13 3 M5 R8 5 2 0 to 2 5 17 7 to 22 1 M6 R8 6 4 0 to 5 0 35 4 to 44 3...

Страница 32: ...rload Protection Set parameter E2 01 motor rated current to the appropriate value to enable motor overload protection The internal motor overload protection is UL listed and in accordance with the NEC...

Страница 33: ...e the motor overload protection L1 01 1 2 or 3 when connecting the drive to a sin gle motor unless there is another means of preventing motor thermal overload The elec tronic thermal overload function...

Страница 34: ...l load amp rating E2 01 Adjusting the value of L1 02 can shift the set of OL1 curves up the Y axis of the diagram below but will not change the shape of the curves L1 03 Motor Overload Alarm Operation...

Страница 35: ...e back cover Date of Publication Rev No Section Revised Contents January 2008 First edition June 2009 Back cover Revision Address May 2010 Chapter 8 Instructions for UL and cUL MANUAL NO TOEP C710606...

Страница 36: ...ITED KINGDOM YASKAWA ELECTRIC EUROPE GmbH Unit 3 Centurion Court Brick Close Kiln Farm Milton Keynes Bucks MK11 3JB United Kingdom Phone 44 0 1908 556815 Fax 44 0 1908 565891 Internet http www yaskawa...

Отзывы: