The SI-P1 card can be mounted on these inverters.

VS-616G5:Standard series (Operates on inverter software No.S1042 or later edition)
Varispeed F7:Standard series
Varispeed G7:Standard series

Description

Code No.

Function

SI-P1

PROFIBUS-DP

Communication

Interface Card SI-P1

73600-C033X PROFIBUS data

Extended data 1 (Data length:32 bytes)
High-speed I/O data area (input:16bytes, output
16bytes)
MEMOBUS message (input:16bytes, output 16bytes)

Extended data 2 (Data length:12bytes)
High-speed I/O data area (input:4bytes, output 4bytes)
MEMOBUS message (input:8bytes, output 8bytes)

Basic data (Data length:6 bytes)
High-speed I/O data area (input:6bytes, output 6bytes)

Communication speed:9.6kbps to 12Mbps

 

    

 : 

Before Use

(1)

 

Read this instruction manual and the instruction manual of the inverter on which the PROFIBUS-
DP Communications Interface Card SI-P1 is to be mounted before using the PROFIBUS-DP
Communications Interface Card SI-P1

(2)

 

Connect the PROFIBUS-DP communications interface card SI-P1 to the connectors or external
terminals where the inverter power supply is turned OFF and the inverter CHARGE indicator
lamp is extinguished.

(3)

 

Specify the name and code number when placing an order of the PROFIBUS-DP communications
interface card SI-P1.

Fig. 1    PROFIBUS-DP Communications Interface Card SI-P1

NOTE

Connector with Inverter
Control Board (JP1)

PROFIBUS-DP

Bus Connection

Terminal (JP3)

Termination

Resistor

Selector

Switich

Address Switch 2

(

×

10)

Address Switch 1

(

×

1)

Ground Lead
Wire

Status Display LED

Spacer
Mounting Hole

Model and
Code No.

SI-P1

73600-C0331

AUDIN - 7 bis rue de Tinqueux - 51100 Reims - France

Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

Содержание 73600-C033X

Страница 1: ...AUDIN 7 bis rue de Tinqueux 51100 Reims France Tel 03 26 04 20 21 Fax 03 26 04 28 20 Web http www audin fr Email info audin fr ...

Страница 2: ...cribed in the relevant sections CAUTION A CMOS IC is used for the Option Card Handle the control board and CMOS IC carefully The CMOS IC can be destroyed by static electricity if touched directly To remove this option card from the inverter and transport or store it separately keep the option card in the anti static electricity package used to protect the unit at delivery Do not change the wiring ...

Страница 3: ...the instruction manual of the inverter on which the PROFIBUS DP Communications Interface Card SI P1 is to be mounted before using the PROFIBUS DP Communications Interface Card SI P1 2 Connect the PROFIBUS DP communications interface card SI P1 to the connectors or external terminals where the inverter power supply is turned OFF and the inverter CHARGE indicator lamp is extinguished 3 Specify the n...

Страница 4: ...front cover Confirm that the CHARGE indicator lamp is extinguished 2 Fit the SI P1 card connector JP1 to the connector 2CN number of pins 60P on the inverter control board At this time insert the two SI P1 card spacer mounting holes into the option card spacer on the control board until a click is heard and mount the SI P1 card firmly See part in the side view 3 Connect the ground lead wire to the...

Страница 5: ... Option D Connector Control Terminal Ground Terminal E G Ground Terminal E Inverter Control PC board Option A Option C Option D SI P1 Front View For F7 Series Side View For F7 Series A 4CN Option A Connector 2CN Option C Connector Fig 2 Installation of PROFIBUS DP Communications Interface Card SI P1 AUDIN 7 bis rue de Tinqueux 51100 Reims France Tel 03 26 04 20 21 Fax 03 26 04 28 20 Web http www a...

Страница 6: ...ir cable conforming to the PROFIBUS specifications for the communications cable NOTE 8 3 R D T D N R D T D P 9 pin D SUB 1 2 3 4 5 6 R D T D N R D T D P Shield SI P1 Card Inverter Bus Connection Terminal PROFIBUS DP Master 2CN 60P PE 12 R L1 S L2 T L3 U T1 V T2 W T3 M 2CN 60P 3 phase Power Supply P Motor JP3 G5 series use terminal 12 F7 series use terminal E G AUDIN 7 bis rue de Tinqueux 51100 Rei...

Страница 7: ...5 28 16 8 160 UL 30 14 8 300 CSA 28 16 8 300 2 Refer to Fig 4 for an illustration of how the end of the connecting cable on the SI P1 card s side should be prepared 3 Use a thin screwdriver less than 2 5mm wide and less than 0 4mm thick to loosen the terminal screw 4 Connect the SI P1 card s terminal block No 3 with the PROFIBUS DP master s No 8 pin and connect the SI P1 card terminal block No 4 w...

Страница 8: ...sion line When the SI P1 card is connected as the end unit of the communications line the termination resistor selector switch ON of the SI P1 card will connect the termination resistor Termination resistors do not have to be mounted externally 5 1 3 Setting of Communications Speed When the communications speed is set on the PROFIBUS DP master the speed for the SI P1 card is also automatically set...

Страница 9: ...eleration stop using deceleration time in C1 02 1 Coast to stop 2 Emergency stop using deceleration time in C1 09 3 Continue operation 2 1 F6 02 Input level of external error from Communications Option Card 0 Always detect 1 Detect during operation 0 F6 03 Stopping method for external error from Communications Option Card 0 Deceleration stop using deceleration time in C1 02 1 Coast to stop 2 Emerg...

Страница 10: ... method selection 1 b1 02 Run Source 0 Digital Operator 1 Control circuit terminals sequence inputs 2 MEMOBUS communications usingSI K2 3 Option Card 4 MEMOBUS communications for CP 717 1 External Fault Input Level from Optical option F9 01 E 15 Selection 0 NO contact external fault at 1 1 NC contact external fault at 0 0 External Fault from Optical Option F9 02 EF0 Detection 0 Always detect 1 Det...

Страница 11: ...e GSD file version is different Previous GSD file Revision Version1 0 New GSD file Revision Version3 1 Contact your Yaskawa representative to get the new GSD file for SI P1 card The new GSD file Version3 1 for SI P1 card is applicable to both the SI P1 card and the SI P card GSD files Version1 0 Version3 1 SI P card Applicable Applicable SI P1 card Not applicable Applicable AUDIN 7 bis rue de Tinq...

Отзывы: