background image

PPC | 67S-RTP0 | Manual

HB160 | PPC | 67S-RTP0 | en | 22-22

HMI

Panel PC - PPC021 IE

Содержание 67S-RTP0

Страница 1: ...PPC 67S RTP0 Manual HB160 PPC 67S RTP0 en 22 22 HMI Panel PC PPC021 IE...

Страница 2: ...67S RTP0_000_PPC021IE 2 EN 2022 YASKAWA Europe GmbH Hauptstra e 185 65760 Eschborn Germany Tel 49 6196 569 300 Fax 49 6196 569 398 Email info yaskawa eu com Internet www yaskawa eu com...

Страница 3: ...3 5 Operating system Windows 10 IoT Enterprise 31 3 5 1 General 31 3 5 2 Structure 32 4 BIOS Setup 38 4 1 Overview 38 4 2 Main 39 4 3 Advanced 40 4 4 Chipset 50 4 5 Boot 55 4 6 Security 56 4 7 Save a...

Страница 4: ...products mentioned are registered trademarks of Microsoft Inc USA All other trademarks logos and service or product marks specified herein are owned by their respective companies Every effort has bee...

Страница 5: ...edge of automation technology n The manual consists of chapters Each chapter describes a completed topic n The following guides are available in the manual An overall table of contents at the beginnin...

Страница 6: ...ion department n commissioning n operation CAUTION The following conditions must be met before using or commis sioning the components described in this manual Hardware modifications to the process con...

Страница 7: ...odules that have been damaged by electrostatic discharges can fail after a temperature change mechanical shock or changes in the electrical load Only the consequent implementation of protection device...

Страница 8: ...T panel 16 7 M colour n PCAP multitouch n Display resolution 1920 x 1080 n Processor Baytrail Intel Celeron J1900 Quad core 2GHz n Work memory 8GB n User memory 64GB SSD iSLC n CFast slot n 2 RS232 RS...

Страница 9: ...SB 3 0 7 2x USB A interface USB 2 0 8 RJ45 jack for Ethernet communication LAN 2 9 RJ45 jack for Ethernet communication LAN 1 10 2 pin connector for remote Power switch 11 3 5mm Audio Line out 12 Powe...

Страница 10: ...e make sure that the Panel PC always has to be supplied with external voltage 1 Slot for CFast storage media 2 Power switch pushbutton The Panel PC starts automatically when the power supply is switch...

Страница 11: ...d an according DC 24V slot at the back The power supply is protected against inverse polarity and overcurrent The matching 3 pin plug con nector is included in the scope of delivery VGA SubD HD15 jack...

Страница 12: ...kbit s RS422 interface n Logical conditions as voltage difference between 2 twisted lines n Serial bus connection full duplex four wire operation n Line length 250m at 115 2kbit s 1200m at 19 2kbit s...

Страница 13: ...HMI Hardware description Structure Interfaces HB160 PPC 67S RTP0 en 22 22 13...

Страница 14: ...twisted pair cable required for Ethernet LEDs Activity yellow Link green Link orange Description blinks 1000Mbit s link blinks 100Mbit s link blinks 10Mbit s link or no link not active At this connect...

Страница 15: ...of the Panel PC there is a card slot for a memory card At this slot you can plug storage modules of the type CFast 2 0 600 MB s 6GBit s SATA protocol not hot swap compatible Pin Assignment Pin Assignm...

Страница 16: ...l W x H x D 542 x 362 x 54 20mm Installation depth 54 20mm The degrees of protection are only guaranteed when the following is observed The material thickness of the installation cut out is 3 12mm The...

Страница 17: ...reference earth Inputs outputs AC DC 50V test voltage AC 500V Protective measures against short circuit Environmental conditions to EN 61131 2 Climatic Storage transport EN 60068 2 14 20 75 C Operati...

Страница 18: ...with lightning protection elements like conductors for lightning and overvoltage is necessary 2 6 Use in difficult operating conditions Without additional protective measures the products must not be...

Страница 19: ...max deviation per day 10 s Operating controls Touchscreen PCAP Touch function Multi Touch Keyboard external via USB Mouse external via USB Interfaces MPI PROFIBUS DP MPI PROFIBUS DP connector Serial C...

Страница 20: ...ta Housing Protection class Material coated aluminium steel plate Mounting via integrated pivoted lever Protection class IP front side IP 66 Protection class IP back side IP 20 Protection class NEMA f...

Страница 21: ...Order no 67S RTP0 KB Certifications UL certification yes KC certification HMI Hardware description Technical data 67S RTP0 KB HB160 PPC 67S RTP0 en 22 22 21...

Страница 22: ...ting tableau and control cabinet fronts the Panel PC requires the following front panel cutting Panel PC W x H in mm 67S RTP0 547 x 367mm The material thickness of the installation cut out is 3 12mm F...

Страница 23: ...pulling the plate 2 With the label facing up insert the CFast card until it is completely seated in the slot and reinstall the cover plate After installation the CFast card is automatically recognize...

Страница 24: ...at during operation the device must not be laid open to direct sun light After opening the control cabinet or desk there are parts with pos sible dangerous voltage available For all signal connections...

Страница 25: ...this button within this time the project will start If the time expires the project will start automatically With the button Main you get to the selection menu n A delay time of 5 seconds is default I...

Страница 26: ...nified Write Filter UWF Settings you can make settings for the Unified Write Filter For this the Unified Write Filter must be deactivated default Setting and activating the Unified Write Filter is onl...

Страница 27: ...althreshold Under Overlay Consumption you can see how much memory has already been consumed n To execute the firmware update press the button Info Update After clicking Info Update the current image i...

Страница 28: ...anager With Back you can return to the select menu By default the configuration of the Startup Manager the registry settings for the back light the local settings and the LAN settings will be saved by...

Страница 29: ...of your Panel PCs via the Info Update button By default Windows 10 IoT Enterprise is automatically activated the first time it is con nected to the Internet An active internet connection is required...

Страница 30: ...time version of the HMI SCADA project engineering platforms your project is run able n By using the according communication driver the Panel PC supports connecting options to the PLC via Ethernet n Du...

Страница 31: ...at the touch screen this area is recognized and the pro gram reacts accordingly The following types of entry are differentiated n Double click A double click has to be executed like mouse operation by...

Страница 32: ...r supply UPS In the event of a power failure this continues to supply the Panel PC until it can be shut down properly 3 5 2 Structure 1 Icon Via icons on the desktop you gain direct access to the appl...

Страница 33: ...rd allows you to enter key entries without connecting an external keyboard As soon as an entry is required the software keyboard is automatically shown Select the button Software keyboard in the lower...

Страница 34: ...Here you can make all settings n System properties Via Windows Start Settings System Info you receive information about the version of the current Windows operating system and the copyright n Allow re...

Страница 35: ...r Accounts window opens 2 In the opening dialog window check the box User must enter a user name and password to use this computer and confirm with Apply You can also change the password in this secti...

Страница 36: ...r must enter a user name and password to use this computer and choose the user which should be automatically logged in after booting Confirm with Apply 3 The window for entering the login data opens E...

Страница 37: ...ted user Confirm with OK and in the next window again with OK The next start up takes place without requesting the log in data HMI Deployment Panel PC Operating system Windows 10 IoT Enterprise Struct...

Страница 38: ...s n Making changes to the power management configuration n Changing the password or making other changes to the security setup Normally CMOS setup is needed when the system hardware is not consistent...

Страница 39: ...Saves and exits the setup program Enter Enters the highlighted submenu When 4 appears on the left of a particular field it indicates that a submenu which contains addi tional options are available fo...

Страница 40: ...format is hour minute second n hour displays hours from 00 to 23 n minute displays minutes from 00 to 59 n second displays seconds from 00 to 59 4 3 Advanced This menu allows you to configure the syst...

Страница 41: ...This section is used to configure Advanced Configuration and Power Interface ACPI Settings Submenu ACPI Settings HMI BIOS Setup Advanced HB160 PPC 67S RTP0 en 22 22 41...

Страница 42: ...when the suspend button is pressed Suspend Disabled Sleep state disabled S3 Suspend to RAM Standby mode enabled Windows saves the system state in RAM This section is used to configure serial ports En...

Страница 43: ...Displays the Super I O Chip used on the board This section is used to configure serial port 1 Super IO Chip Submenu Serial Port 1 Configuration HMI BIOS Setup Advanced HB160 PPC 67S RTP0 en 22 22 43...

Страница 44: ...resistor Disabled Terminal resistor not activated Enabled default Terminal resistor activated This section is used to configure serial port 2 Enables or disables the serial port Disabled Serial port...

Страница 45: ...Terminal resistor not activated Enabled default Terminal resistor activated This section Pc Health Status is used to configure the hardware temperature and vol tages This section is used to configure...

Страница 46: ...unctions are supported Enabled Limit the return value to 3 or less than 3 XD can prevent certain classes of malicious buffer overflow attacks Enabled Permit the switching on of the execute disable fun...

Страница 47: ...This section is used to configure the Processor Power Management PPM configuration Submenu PPM Configu ration HMI BIOS Setup Advanced HB160 PPC 67S RTP0 en 22 22 47...

Страница 48: ...to use AHCI Advanced Host Con troller Interface AHCI allows the storage driver to enable the advanced serial ATA features which will increase storage performance Enables or disables SATA port 0 Enabl...

Страница 49: ...pplications Enabled Default Enables USB 3 0 controller support Disabled Disables USB 3 0 controller support Enabled Enables XHCI USB 3 0 or EHCI USB 2 0 support Disabled Disables XHCI USB 3 0 or EHCI...

Страница 50: ...this option only when changing the panel otherwise the display may not work The options are Tact Switch Manual and Light Sensor The default setting is Manual and the Backlight option below will be co...

Страница 51: ...te where you left off before power failure occurs Power Off The system s power is off You must press the power button to Power On the system Power On default The system will automatically Power On Thi...

Страница 52: ...e Disabled Azalia will be unconditionally disabled Enabled Azalia will be unconditionally enabled Enables or disables internal HDMI Codec for Azalia Audio Controller Azalia HDMI Codec HMI BIOS Setup C...

Страница 53: ...e EHCI con troller must always be enabled Enables or disables PCH USB rate matching hubs mode Enables or disables PCH EHCI debug capability Submenu USB Configura tion USB 2 0 EHCI Support USB RMH Mode...

Страница 54: ...Enables or disables the PCI Express ports 0 3 on the chipset Submenu PCI Express Configuration PCI Express Port 0 PCI Express Port 3 HMI BIOS Setup Chipset HB160 PPC 67S RTP0 en 22 22 54...

Страница 55: ...ll decrease the time needed to boot the system Controls the execution of UEFI and legacy PXE OpROM Enables or disables the boot option for legacy network devices connected to LAN1 or LAN2 Disabled def...

Страница 56: ...when entering setup If only the User s password is set then this is a power on password and must be entered to boot or enter setup In Setup the user will have administrator rights If ONLY the Adminis...

Страница 57: ...east 3 characters and should be maximal 20 characters long Select this to reconfigure the user s password Your password must contain at least 3 characters and should be maximal 20 characters long Admi...

Страница 58: ...nfirm again before exiting The BIOS setup exits and a restart follows To restore the BIOS to default settings select this field then press Enter A dialog box will appear Confirm by selecting Yes To sa...

Страница 59: ...rd phishing The most important precautions to prevent manipulation and loss of data security in the industrial environment are n Encrypting the data traffic by means of certificates n Filtering and in...

Страница 60: ...he communication ports that are used for communication should be acti vated Only the communication protocols that are used for communication should be activated n Consider possible defence strategies...

Страница 61: ...ected against manipulation n Use encryption systems on your storage media n Perform security assessments regularly to reduce the risk of manipulation n Use only data and software from approved sources...

Страница 62: ...use Typical source Galvanic coupling Galvanic or metallic coupling always occurs when two current circuits have a common line n Pulsed devices Net influence from transducers and foreign net devices n...

Страница 63: ...extensive and impedance low Please try not to use aluminium parts Aluminium is easily oxidizing and is there fore less suitable for grounding n When cabling take care of the correct line routing Organ...

Страница 64: ...ing actions The grounding of the PLC serves for protection and functionality activity Connect installation parts and cabinets with your PLC in star topology with the isolation protected earth conducto...

Страница 65: ...an error Thus you have to connect the ground with the protected earth conductor To avoid ground loops local distant ground constructions cubicles construction and machine parts have to be connected w...

Страница 66: ...p B Group C Group D Group A 1 2 3 4 Group B 2 1 3 4 Group C 3 3 1 4 Group D 4 4 4 1 1 The lines may be installed in common bundles or cable trusses 2 The lines have to be installed in different bundle...

Страница 67: ...ng conductor must not exceed 10 of the impedance of the screen where screened signal lines are connected between the dif ferent sections of the plant and the screening is connected to ground neutral o...

Страница 68: ...ct the screen to PIN 1 of the connector In case of stationary operations it is recommended that the remove the insulation from the screened cable without cutting the screen and to attach this point to...

Страница 69: ...stor using RC network Every cubicle must be provided with a power outlet for the PU These outlets must be wired to the distribution system which is also used to connect the neutral conductor for the c...

Страница 70: ...ns of grounding straps connected to the body of the cubicle Cable routing Cabling divided into groups Power cables 230 400V and signal lines installed in separate channels or bunches Potential compens...

Страница 71: ...Appendix HMI Appendix HB160 PPC 67S RTP0 en 22 22 71...

Страница 72: ...Content A History of changes 73 HMI Appendix HB160 PPC 67S RTP0 en 22 22 72...

Страница 73: ...es Rev Changes 22 04 The manual was created 22 22 CI adjustment was done Chapter Hardware description n Description Use in difficult operating conditions was added HMI History of changes HB160 PPC 67S...

Отзывы: