Mounting conditions
Mounting place
-
In the control cabinet
Mounting position
-
Horizontal and vertical
EMC
Standard
Comment
Emitted interfer-
ence
EN 61000-6-4
Class A (Industrial area)
Noise immunity
zone B
EN 61000-6-2
Industrial area
EN 61000-4-2
ESD
8kV at air discharge (degree of severity 3),
4kV at contact discharge (degree of severity
2)
EN 61000-4-3
HF field immunity (casing)
80MHz … 1000MHz, 10V/m, 80% AM (1kHz)
1.4GHz ... 2.0GHz, 3V/m, 80% AM (1kHz)
2GHz ... 2.7GHz, 1V/m, 80% AM (1kHz)
EN 61000-4-6
HF conducted
150kHz … 80MHz, 10V, 80% AM (1kHz)
EN 61000-4-4
Burst, degree of severity 3
EN 61000-4-5
Surge, installation class 3 *
*) Due to the high-energetic single pulses with Surge an appropriate external protective circuit with lightning protection elements like conductors
for lightning and overvoltage is necessary.
2.6 Technical data
2.6.1 62E-MGC0-DH
Order no.
62E-MGC0-DH
Type
Touch Panel TP 604LC
Display
Display size (diagonal)
4.3 "
Display size (width)
95 mm
Display size (height)
54 mm
Resolution
272 x 480 / 480 x 272
Aspect ratio
16:9
Type of display
TFT color (64K colors)
MTBF Backlights (25°C)
30000 h
System properties
Processor
Cortex-A8 667 MHz
VIPA HMI
Hardware description
Technical data > 62E-MGC0-DH
HB160 | TP-ECO | 62E-MGC0 | GB | 16-02
19