No.
Parameter Name
Default Setting
C6-01
Drive Duty Selection
1: Normal Duty
C6-02
Carrier Frequency Selection
3: 8.0 kHz
H2-03
Terminals P2 Function Selection
39: Watt Hour Pulse Output
L2-01
Momentary Power Loss Operation Selection
2: CPU Power Active - Drive will restart if power returns prior
to control power supply shut down.
L8-03
Overheat Pre-Alarm Operation Selection
4: Operation at lower speed
L8-38
Carrier Frequency Reduction
2: Enabled across entire frequency range.
Table 4.12 HVAC Fan: User Parameters (A2-01 to A2-16)
No.
Parameter Name
No.
Parameter Name
b1-01
Frequency Reference Selection 1
E1-03
V/f Pattern Selection
b1-02
Run Command Selection 1
E1-04
Maximum Output Frequency
b1-04
Reverse Operation Selection
E2-01
Motor Rated Current
C1-01
Acceleration Time 1
H3-11
Terminal A2 Gain Setting
C1-02
Deceleration Time 1
H3-12
Terminal A2 Bias Setting
C6-02
Carrier Frequency Selection
L2-01
Momentary Power Loss Operation Selection
d2-01
Frequency Reference Upper Limit
L8-03
Overheat Pre-Alarm Operation Selection
d2-02
Frequency Reference Lower Limit
o4-12
kWh Monitor Initialization
u
Setting 5: Compressor Application
Table 4.13 Compressor: Parameter Settings
No.
Parameter Name
Default Setting
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Prohibited
C1-01
Acceleration Time 1
5.0 s
C1-02
Deceleration Time 1
5.0 s
C6-01
Drive Duty Selection
0: Heavy Duty
E1-03
V/f Pattern Selection
0FH
L2-01
Momentary Power Loss Operation Selection
1: Enabled
L3-04
Stall Prevention Selection during Deceleration
1: Enabled
Table 4.14 Compressor: User Parameters (A2-01 to A2-16):
No.
Parameter Name
No.
Parameter Name
b1-01
Frequency Reference Selection 1
E1-03
V/f Pattern Selection
b1-02
Run Command Selection 1
E1-07
Middle Output Frequency
b1-04
Reverse Operation Selection
E1-08
Middle Output Frequency Voltage
C1-01
Acceleration Time 1
E2-01
Motor Rated Current
C1-02
Deceleration Time 1
−
−
u
Setting 6: Preset 6
Note:
1.
Read the instructions listed in
Notes on Controlling the Brake when Using Application Preset 6
on page
when using Application
Preset 6
2.
Perform Auto-Tuning after selecting Application Preset 6.
3.
If UL3 appears on the operator display after Auto-Tuning is complete, set L6-01 to “0” to repeat the Auto-Tuning process.
Table 4.15 Preset 6: Parameters and Settings
No.
Parameter Name
Default Setting
A1-02
Control Method Selection
2: Open Loop Vector Control
b1-01
Frequency Reference Selection 1
0: Operator
4.6 Application Selection
98
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual