H2-06
Watt Hour Output Unit Selection
Sets the output units for the watt hours when
Watt Hour Pulse Output is selected as the digital
output (H2-01, H2-02, or H2-03 = 39).
Outputs a 200 ms pulse signal when the watt-
hour counter increases by the units selected.
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
0 to 4
0
A A A
437
<1> The availability of certain functions depends on the control method used.
H2 Multi-Function Digital Output Settings
H2-
oo
Setting
Function
Description
Control
Mode
Pg.
V/
f
O
L
V
P
M
0
During Run
Closed: A Run command is active or voltage is output.
O O O
1
Zero Speed
Closed: Output frequency is 0.
O O O
2
Speed Agree 1
Closed: Output frequency equals the speed reference (plus or minus the hysteresis set
to L4-02).
O O O
3
User Set Speed Agree 1
Closed: Output frequency and speed reference equal the value in L4-01 (plus or minus
the hysteresis of L4-02).
O O O
4
Frequency Detection 1
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis
determined by L4-02.
O O O
5
Frequency Detection 2
Closed: Output frequency is greater than or equal to the value in L4-01, with hysteresis
determined by L4-02.
O O O
6
Drive Ready
Closed: Drive Ready. The drive is powered up, not in a fault state, and in the Drive
mode.
O O O
7
DC Bus Undervoltage
Closed: DC bus voltage is below the Uv trip level set in L2-05.
O O O
8
During Baseblock (N.O.)
Closed: There is no output voltage
O O O
9
Frequency reference selection Open: External Reference 1 or 2 supplies the frequency reference
Closed: Digital operator supplies the frequency reference.
O O O
A
Run command selection
Open: External Reference 1 or 2 supplies the Run command
Closed: Digital operator supplies the Run command.
O O O
B
Torque Detection 1 (N.O.)
Closed: Output current/torque exceeds the torque value set in parameter L6-02 for longer
than the time set in parameter L6-03.
O O O
C
Frequency Reference Loss
Closed: Loss of the analog frequency reference detected. Enabled when L4-05 = 1.
O O O
D
Braking Resistor Fault
Closed: Braking resistor or transistor is overheated or faulted out. This selection requires
that braking resistor protection parameter be set for ERF (L8-01 = “1”).
O O O
E
Fault
Closed: Fault occurred (other than CPF00 and CPF01).
O O O
F
Not used/Through Mode
Set this value when the terminal is not used, or when using the terminal in the pass-
through mode.
O O O
10
Minor Fault
Closed: An alarm is triggered.
O O O
11
Reset Command Active
Closed: The drive has received a reset command from the multi-function input terminals
or from serial network, or the digital operator RESET key has been pressed.
O O O
12
Timer Output
Timer output, controlled by b4-01 and b4-02. Used in conjunction with the digital input
(H1-
oo
= 18 “timer function”).
O O O
13
Speed Agree 2
Closed: When drive output frequency equals the frequency ref/- L4-04.
O O O
14
User Set Speed Agree 2
Closed: When the drive output frequency is equal to the value in L4-03 (plus or minus
L4-04).
O O O
15
Frequency Detection 3
Closed: When the drive output frequency is less than or equal to the value in L4-03 with
the hysteresis determined by L4-04.
O O O
16
Frequency Detection 4
Closed: When the output frequency is greater than or equal to the value in L4-03 with
the hysteresis determined by L4-04.
O O O
B.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
379