2.6 Wiring power modules
Power modules are either integrated to the head module or may be installed between the
periphery modules. With power modules, terminals with spring clamp technology are
used for wiring. The spring clamp technology allows quick and easy connection of your
signal and supply lines. In contrast to screw terminal connections this type of connection
is vibration proof.
U
max
30V DC
I
max
10A
Cross section
0.08 ... 1.5mm
2
(AWG 28 ... 16)
Stripping length 10mm
1
Pin number at the connector
2
Opening for screwdriver
3
Connection hole for wire
1.
Insert a suited screwdriver at an angel into the square opening as shown. Press
and hold the screwdriver in the opposite direction to open the contact spring.
2.
Insert the stripped end of wire into the round opening. You can use wires with a
cross section of 0.08mm
2
up to 1.5mm
2
3.
By removing the screwdriver, the wire is securely fixed via the spring contact to the
terminal.
Terminal module terminals
Data
Wiring procedure
VIPA System SLIO
Basics and mounting
Wiring power modules
HB300 | CP | 040-1CA00 | en | 18-28