Yamatake Neostat T6065 Series Скачать руководство пользователя страница 4

4

AB-5881

Fig. 5  Attach/detach cover

Fig. 6  Install Neostat

Wiring

All wiring must comply with local electrical codes and
ordinance.    In general these codes require:

1. Wire no smaller than #14 (1.6 mm).
2. All terminal connections should be carefully made.    In

making surface wiring, use knockout on the top of the
body where marked.

3. Make correct wiring.    Check the screw terminals for

loose connections.

Fig.7  Connection diagram

Setting

1. Remove the cover.
2. T6065B and T9065B have S/W changeover switch.

Set the lever in the specified position.    See Fig. 10.
Note: When the equipment is energized, do not

change the switch.

3. The temperature controller have setpoint stoppers

(Fig. 8) and the humidity controller have a setpoint
lock screw (Fig. 9). The Neostat is shipped from the
factory with setpoint dial locked in the position as
follows:
Temperature controller

30 °C

Humidity controller 30 to 80 % RH model

80 % RH

50 to 90 % RH model

90 % RH

After sliding the stoppers of the temperature controller
or after loosening the lock screw of the humidity
controler, adjust the setpoint dial to the desired
temperature or humidity.    Setpoint is the center of
throttling range for proportional controllers.    For two-
position controllers, see Figs. 11 and 12.

4. Set the setpoint stoppers or a lock screw as occasion

calls.

5. Replace the cover.

Push spring plate
for opening

Cover

Neostat

Baseplate

T9065B

R

W

R

B

W

B

S/W changeover SW

S/W changeover SW

T6065B

R

W

R

B

(Summer)

B

H615A

R

Humidifi-

cation

Dehumidi-

fication

B

W

T6065A

Rise

R

Cooling

Heating

W

B

H915A

R

B

W

T9065A

R

W

B

Rise

Rise

Rise

Rise

Rise

(Winter)

S

W

(Summer)

(Winter)

S

W

Clutch, push down and
fasten using the
Neostat mounting
screw shown in the
Fig.3 and Fig4.

Back of Neostat

Baseplate

Содержание Neostat T6065 Series

Страница 1: ...tions 20 to 50 C 95 RH or less Differenitial T6065A B Approx 1 C fixed H615A Approx 5 RH fixed H615A2036 at 50 RH H615A2044 at 65 RH Throttling range T9065A B Approx 2 C fixed H915A Approx 12 RH fixed at 50 RH Element Temperature controller Diaphragm Humidity controller Nylon ribbon Item Specifications Cover Pale beige equivalent to Munsell 5Y8 1 Base Dark gray equivalent to Munsell N3 0 Attachmen...

Страница 2: ...duct is targeted for general air conditioning Do not use this product in a situation where human life may be affected If this product is used in clean rooms or places where reliability or control accuracy is particularly required please contact Yamatake s sales representatives Yamatake Building Systems Co Ltd bears no responsibility for any benefit or lack of benefit derived from the operation by ...

Страница 3: ... plate 2 Mount the terminal block on the baseplate 3 Wire the terminal block Refer to wiring section 4 Remove the cover See Fig 5 Then put the Neostat on the baseplate See Fig 6 and mount to the terminal block 5 Replace the cover Fig 4 Mounting thermo plate Cover Neostat mounting screw M3 L 8 Terminal block mounting screw M2 6 8 Tapping screw 2 Neostat Terminal block Baseplate mounting screw Basep...

Страница 4: ...the factory with setpoint dial locked in the position as follows Temperature controller 30 C Humidity controller 30 to 80 RH model 80 RH 50 to 90 RH model 90 RH After sliding the stoppers of the temperature controller or after loosening the lock screw of the humidity controler adjust the setpoint dial to the desired temperature or humidity Setpoint is the center of throttling range for proportiona...

Страница 5: ...ew the setpoint can be fixed Undo the setpoint lock Turn the lock screw about two turns counter clockwise Lock the setpoint Set the setpoint dial to the desired temperature and turn the lock screw about two turns clockwise Note When the equipment is energized do not move S W changeover switch Summer winter changeover switch Summer winter indication S Summer W Winter Makes R B Humidity rise Makes R...

Страница 6: ...ternational Business Headquarters Totate International Building 1 12 19 Shibuya Shibuya Ku Tokyo 150 8316 URL http www yamatake com First Printing Dec 2000 Printed in Japan AB 5881 3H H W Specifications are subject to change without notice ...

Отзывы: