Specifications

Temperature Controllers

Model

Control

Provided

Range

Summer-winter

changeover switch

T6065A2026

No

T6065B2024

Two-position

Yes

T9065A2020

No

T9065B2028

Proportional

15 to 30 °C

Yes

Humidity Controllers

Model

Control Provided

Range

H615A2036

30 to 80 % RH

H615B2044

Two-position

50 to 90 % RH

H915A2022

Proportional

30 to 80 % RH

Electrical rating:
  T6065A, B

125 V AC

250 V AC

Full load

6 A

3 A

Locked rotor

36 A

18 A

  H615A

Dehumidification

Humidification

125 V AC 250 V AC 125 V AC 250 V AC

Full load

3.0 A

1.5 A

4.4 A

2.2 A

Locked rotor

18.0 A

9.0 A

26.4 A

13.2 A

Resistive load

8.0 A

4.0 A

Item

Specifications

Rated operat-
ing conditions

15 to 40 °C (95 % RH or less)

Transport/
storage
conditions

–20 to 50 °C (95 % RH or less)

Differenitial

T6065A,B : Approx. 1 °C fixed
H615A

: Approx. 5 % RH fixed

(H615A2036 : at 50 % RH,
 H615A2044 : at 65 % RH)

Throttling range T9065A,B : Approx. 2 °C fixed

H915A

: Approx. 12 % RH fixed

(at 50 % RH)

Element

Temperature controller : Diaphragm
Humidity controller : Nylon ribbon

Item

Specifications

Cover

Pale beige (equivalent to Munsell 5Y8/1)

Base

Dark gray (equivalent to Munsell N3.0)

Attachment

Terminal block: 1

Mounting screw between body and termi-
nal

 

block (M3x8): 1

Tapping screw for mounting terminal block
(M2.6x8): 2

Auxiliary
(order sepa-
rately)

Base plate

Q6065A1007....... T6065A
Q6065B1005....... T6065B
Q9065A1001....... T9065A
Q9065B1009....... T9065B
Q6150A1003....... H615A
Q9150A1007....... H915A

Thermo plate for individual room control

QY11A01J1

Thermo plate

DY2000A1003 (One unit, horizontal
mounting)
DY2000A1002 (One unit, vertical mount-
ing)
DY2000A2003 (Two unit, horizontal
mounting)
DY2000A2002 (Two unit, vertical mount-
ing)

Multi-thermo case

TY110A

Specifications/Instructions

With baseplate and mounting plate model

Содержание Neostat T6065 Series

Страница 1: ...tions 20 to 50 C 95 RH or less Differenitial T6065A B Approx 1 C fixed H615A Approx 5 RH fixed H615A2036 at 50 RH H615A2044 at 65 RH Throttling range T9065A B Approx 2 C fixed H915A Approx 12 RH fixed at 50 RH Element Temperature controller Diaphragm Humidity controller Nylon ribbon Item Specifications Cover Pale beige equivalent to Munsell 5Y8 1 Base Dark gray equivalent to Munsell N3 0 Attachmen...

Страница 2: ...duct is targeted for general air conditioning Do not use this product in a situation where human life may be affected If this product is used in clean rooms or places where reliability or control accuracy is particularly required please contact Yamatake s sales representatives Yamatake Building Systems Co Ltd bears no responsibility for any benefit or lack of benefit derived from the operation by ...

Страница 3: ... plate 2 Mount the terminal block on the baseplate 3 Wire the terminal block Refer to wiring section 4 Remove the cover See Fig 5 Then put the Neostat on the baseplate See Fig 6 and mount to the terminal block 5 Replace the cover Fig 4 Mounting thermo plate Cover Neostat mounting screw M3 L 8 Terminal block mounting screw M2 6 8 Tapping screw 2 Neostat Terminal block Baseplate mounting screw Basep...

Страница 4: ...the factory with setpoint dial locked in the position as follows Temperature controller 30 C Humidity controller 30 to 80 RH model 80 RH 50 to 90 RH model 90 RH After sliding the stoppers of the temperature controller or after loosening the lock screw of the humidity controler adjust the setpoint dial to the desired temperature or humidity Setpoint is the center of throttling range for proportiona...

Страница 5: ...ew the setpoint can be fixed Undo the setpoint lock Turn the lock screw about two turns counter clockwise Lock the setpoint Set the setpoint dial to the desired temperature and turn the lock screw about two turns clockwise Note When the equipment is energized do not move S W changeover switch Summer winter changeover switch Summer winter indication S Summer W Winter Makes R B Humidity rise Makes R...

Страница 6: ...ternational Business Headquarters Totate International Building 1 12 19 Shibuya Shibuya Ku Tokyo 150 8316 URL http www yamatake com First Printing Dec 2000 Printed in Japan AB 5881 3H H W Specifications are subject to change without notice ...

Отзывы: