AMX Control Module for: MTX5-D Matrix Processor 

Rev.1

3

Tips and Communication Behaviors

We highly recommend using IP control rather than RS232.  Because the AMX system knows when an IP socket is 
dropped, the module can properly re-scan features and ensure status information is current if the connection is lost.  
Using RS232, if the MTX5-D is restarted or the cable is interrupted, it is more difficult to know if the connection was 
lost and things can fall out of sync.

Command to turn communications on:  The MTX5-D will not respond on the control port until it receives a wakeup 
string of “

’devstatus runmode’,$10

”.  If you are using IP, the module sends this string as soon as the IP 

socket opens.  

When using RS232, AMX can’t be sure if the product is online or offline.  (Anytime the power is cycled on the 
MTX5-D, this string will need to be resent.)  We have added a routine to automatically send the wake-up string after 
every minute of silent communication between the controller and MTX5-D, but if you cycle power on the MTX5-D, it 
may be a short while between the MTX5-D finishing boot-up and the serial port becoming available.  If you prefer to 
send a command to the module, you can send ‘WakeUp’ and the module will then send the string for you.

Efficient communications model:  The MTX5-D automatically sends status updates any time parameters 
change.  For instance, if you change volume from this module, a wall controller or MTX editor, status updates are 
automatically generated.  The same goes for presets – all status changes will be updated for you.  However, you 
should be aware that the system will not give you a status update if you send a command that doesn’t change a 
value.  For instance, if you ask for volume at 50% and it was already at 50%, no status string will be returned.

Содержание MTX5-D

Страница 1: ...AMX Control Module for MTX5 D Matrix Processor Rev 1 Release December 10 2014 ...

Страница 2: ...ion Note Customer must provide the 9 pin connector female housing female pins that is supplied with the lens AMX doesn t currently carry this connector 9 Pin D Sub Female AMX 41 0903 WITH AMX 41 0902 HOOD Revision Rev 1 Legend GND Ground RXD Receive Data TXD Transmit Data Connector Type 9 Pin D Sub Female Type of Control RS 232 2 RXD 3 TXD 5 GND RED WHT BLK TXD 3 RXD 2 GND 5 Revision Rev 1 Legend ...

Страница 3: ... cycled on the MTX5 D this string will need to be resent We have added a routine to automatically send the wake up string after every minute of silent communication between the controller and MTX5 D but if you cycle power on the MTX5 D it may be a short while between the MTX5 D finishing boot up and the serial port becoming available If you prefer to send a command to the module you can send WakeU...

Страница 4: ...o streamline that the UI module has the parsing routine in a DATA_EVENT for every feature supported in the COMM module That should reduce the amount of time required for status updates In general controlling binary values like an on off or mute button will use settings of 0 1 or T for toggle The MTX does not have a native toggle command but our COMM module tracks the status and sends the appropria...

Страница 5: ...f 12dB Oct 6 HPF High Pass Filter 7 LPF Low Pass Filter Audio Source 0 Disconnect 1 8 Analog Mic Line 1 8 9 12 Analog Stereo In 1L 2R 13 14 SD Card Player 15 30 YDIF 1 16 31 46 Dante 1 16 47 62 Card Slot 1 16 Meter Groups to Start Stop 1 Analog Input Meters Mic Line 1 8 St In 1L 2R 2 Input Channels Post EQ Inputs 1 30 3 Input Channels Post On Inputs 1 30 4 Effect Returns Effect 1L 2R 5 Matrix Zone...

Страница 6: ...Delay 1 10 sec HSOFF XOFF SET BAUD 38400 115200 N 8 1 485 DISABLE Sets parameters for the module to connect to the MTX5 D For IP you will want to send in the IP address and other IP settings as shown then turn on channel 250 on vdvCom Whenever channel 250 is on the module tries to keep the IP socket connected If the connection is lost the module will automatically attempt to re establish the link ...

Страница 7: ...s the status of each parameter and sends a discrete command to raise or lower the value by these increments If you want larger steps for these commands you could send this in when the module comes online Set StatusSyncInterval msec default 250 When the control port comes online the module begins a timeline to scan the status of all tracked features on the MTX5 D This adjusts the polling interval o...

Страница 8: ... Input AGC NoiseGate In 0 1 T Input AGC On In 0 1 T Input AGC In 1 8 ResponseTime 0 1000 Level 0 1000 NoiseGate 0 Off 1 On On 0 Off 1 On Input Comp Threshold In 0 1000 Input Comp Ratio In 0 1000 Input Comp Knee In 0 1000 Input Comp Attack In 0 1000 Input Comp Release In 0 1000 Input Comp Gain In 0 1000 Input Comp On In 0 1 T Input Comp In 1 16 25 28 Threshold 0 1000 Ratio 0 1000 Knee 0 1000 Attack...

Страница 9: ... InputDCA Volume In DCA 0 1000 InputDCA Mute In DCA 0 1 T InputDCA In 1 8 Vol 0 1000 Mute 0 UNMUTED 1 MUTED MatrixOutput Volume MatrixOut 0 1000 MatrixOutput On MatrixOut DCA 0 1 T MatrixOutput Out 1 16 Vol 0 1000 On 0 Off 1 On MatrixSend Volume In Send 0 1000 MatrixSend On In Send 0 1 T MatrixSend In 1 34 Send 0 16 Vol 0 1000 On 0 Off 1 On Meters Start Meter Group Level Hold Refresh Interval msec...

Страница 10: ...v 1 10 Send Commands Status Strings Output Volume Out 0 1000 Output On Out 0 1 T Output Out 1 16 Vol 0 1000 On 0 Off 1 On OutputDCA Volume Out 0 1000 OutputDCA Mute Out 0 1 T OutputDCA Out 1 8 Vol 0 1000 Mute 0 UNMUTED 1 MUTED Preset 1 50 Preset 1 50 ...

Отзывы: