IOEM/REM Safey and Installation Guide
74
IOEM/REM Safey and Installation Guide
75
IOEM systems management window mode pulldown menu
Configure 5X00 E-Aux system for IOEM input
1.
Follow steps 1-6 of hardware installation-starting on page 25;
2.
Wire IOEM I/O for desired input type-
3.
Verify all steps at Using AquaManager for IOEM configuration - page
73 are completed
4.
Open AquaManager>open 5X00 node window>
;
5.
Select E-Aux 1-8 tab to be configured.
6.
Configure E-Aux system fields;
Notes:
-
IOEM Source channels are only available once IOEM mode has been
uploaded using AquaManager-page 73;
-
IOEM Sources will only be available at IOEM and channel mode pull-
down menus that have been configured as the same input type as the
“IOEM Desired Selection” field for the E-Aux system being configured;
-
Proper wiring of IOEM I/O channels is required in order for IOEM I/O
channels to work correctly.
-
For 5X00 E-Aux configuration information see - AquaManager
Help>Contents tab>Working with Nodes>Systems management>Systems
Management fields table and link to E-Aux bookmarks;
7.
to upload E-Aux system configuration to networked in
-
struments;
Configuring IOEM/REM expansion modules
8.
At the Run Screen verify the configured E-Aux value is properly displayed.
E-Aux system scaling and min/max configuration affect the displayed
value.
5X00 Systems Management Eaux tab non PID control mode
Notes:
-
IOEM input channels can be configured to multiple E-Aux systems;
-
At the Run Screen “Offline” display means the configured IOEM I/O
input/output is a value that the associated 5X00 instrument E-Aux
system does not recognize. An example - if an IOEM channel mode is
configured to digital and the input signal is a 0-1V signal, the reading at
the run screen will be “Offline”;
5X00 instrument run screen when IOEM input value is invalid
-
At the instrument, the IOEM source is configured at the System>E-
Aux>Device Address and Channel menus. See user manual sensor setup
sections, chapter 4 for additional information;
Configuring IOEM/REM expansion modules