en – Original instructions
20
SCUBA – Additional Installation, Operation and Maintenance Instructions
The unit is equipped with built-in capacitor and motor protector, and stops automatically in
case of overtemperature.
After 2-4 minutes the motor protector gives the restart consent.
Overtemperature protection - three-phase motor unit
Install an appropriate motor protector in the control panel, with D curve in accordance with the
current shown in the data plate.
Motor without automatic reset thermal overload protection
1.
If the motor is used with full load, then set the value to the nominal current value on the
data plate.
2.
If the motor is used with partial load, then set the value of the operating current measured
with a current pincer.
4.4.3
Guidelines for the electrical control panel
NOTICE:
The electric panel must match the ratings on the data plate. Improper combinations could
damage the motor.
•
Install appropriate devices for protecting the motor from overloads and short circuits:
Motor
Safety features
Single-phase
•
Automatic reset thermal-ampere protection, built-in (motor protector)
•
From short circuit, by the installer: aM fuses (motor start-up), or thermal magnetic switch
with C curve and Icn ≥ 4.5 kA, or other similar device.
Three-phase
•
Thermal, by the installer: trip class 10 A overload thermal relay + aM fuses (motor start-
up), or start class 10 A motor protection thermal magnetic switch
•
From short circuit, by the installer: aM fuses (motor start-up), or thermal magnetic switch
with C curve and Icn ≥ 4.5 kA, or other similar device.
•
If required, install phase failure sensitive thermal relays.
4.4.4
Operation with frequency converter
Single-phase and three-phase motors can be connected to a frequency converter for speed
control.
•
The converter exposes the insulation of the motor to a greater load, determined by the
length of the connecting cable: observe the requirements of the Manufacturer of the
frequency converter
•
The minimum frequency must not fall below 25 Hz
•
The head of the unit must never be below 2 m (6.5 ft)
•
For applications requiring silent operation, install an outlet filter between the motor and the
converter; a sinusoidal filter can reduce the noise even further
•
The conditions of installation must guarantee protection against voltage peaks between the
terminals and/or dV/dt in the table:
Motor size
Voltage peak, V
dV/dt, V/µs
up to 90R (500 V)
< 650
< 2200
from 90R to 180R
< 1400
< 4600
over 180R
< 1600
< 5200
Otherwise, use a motor with reinforced insulation