en – Original instructions
25
Table 9: Power supply wiring procedure
Reference Figure
e-SM Drive models
103, 105, 107, 111,
115
e-SM Drive models
303, 305, 307, 311,
315, 322
1.
Open the terminal box cover, remove the screws (1).
2.
Use the M20 cable gland for the power cable.
Fig. 7
-
3.
Connect the cable according to the wiring diagram.
4.
Connect the ground (earth) lead. Make sure that the ground (earth) lead
is longer than the phase leads.
5.
Connect the phase leads.
Fig. 10
Fig. 11
-
6.
Close the terminal box cover and tight the screws.
Fig. 7
-
Figure 10: Wiring diagram
Figure 11: Connection label
5.5 I/O connection
WARNING:
Connect the electronic drive only to Safety Extra Low Voltage (SELV) circuits. The circuits
provided for use with external communications and control equipment are designed to provide
isolation from neighboring hazardous circuits within the drive. The communications and control
circuits within the ecocircXL drive are floating from ground and are classified as SELV. They must
be connected only to other SELV circuits in a manner which maintains all the circuits within SELV
limits and prevents ground loops. Physical and electrical separation of the communications and
control circuits from non-SELV electrical circuits must be maintained both within the inverter and
external to the inverters.