Discharge pipe work

On two pump sets the discharge pipe work can be connected to either end of the booster set, ensure the
blanking cap is fitted to the end not used. A flexible connector fitted between the booster discharge manifold
and the system connection pipe will help prevent the transmission of noise/vibration. On single pump units
connect to the port provided. An isolation valve should be provided between the booster discharge line and
the system to aid maintenance. The discharge pipe work should be sized to achieve a maximum velocity of
approximately 2.5m/s.

Pressure vessels

The booster set is fitted with 1 or 2 x 24lt vessels which is the minimum that should be used with fixed speed
pump sets. Larger vessel can be added if required. If stand alone vessels are added they should have an
isolation valve and drain cock fitted to allow the vessel to be isolated from the system and drained to check
the pre-charge pressure.
The vessel pre-charge should be set to approximately 0.2 bar below the pump stating pressure.

Pressure switch setting details

The booster set will be fitted with 1 pressure switch for each pump.
Pump operation is controlled by pressure switches, one for each pump. The unit will normally be
supplied with the pressure switches set to match the pumps fitted.
If pressure switch settings need altering they should be adjusted as follows. Read in conjunction
with fig A
P1s = pump 1 stop pressure which is normally set to 0.5
bar below Pmax (pump closed valve head).
P2s = pump 2 stop pressure which is normally set to 1
bar below Pmax when fitted.
P1 = pump 1 differential pressure which is normally set
at 1 bar, this will start pump one, 1 bar below P1s.
P2 = pump 2 differential pressure which is normally set
at1 bar, this will start pump two 1 bar below P2s when
fitted.

Commissioning

With the main power isolated check:
1. The break tank feeding the set is filled with water and the ball valve is set to the correct height.
2. The set/system vessels have been charged with Nitrogen to the correct pressure (set point -0.2 bar).
3. Open suction line isolation valve.

4. Open suction and discharge pump isolation valves.
5. Close main discharge isolation valve.
6. Open the pump vents at the top of each pump.
7. Allow all air to escape until water flows freely.
8. Close pump vent valves.

9. Open discharge valve.
10. Ensure all vessel valves are open.
11. Switch the main power supply on.
12. allow water to flow and clear air through the system
13. close discharge valve and check pressure reading on pressure gauge
14. The system set point should already be set but to change refer to fig A above.

See GXS O&M for more in depth pump details

.

3

    

Pump 1 

Pump 2

Fig A 

mini f booster set o and m instructions:Layout 1

09/05/2012

15:38

Page 3

Содержание LOWARA F 1-2

Страница 1: ...e noncompliance would affect safety Safety instruction where electrical hazard is involved Safety instruction where noncompliance could cause damage to the equipment Instruction for safe us This product has been designed for boosting cold water in potable water installations to the operating conditions shown This product should not be installed until this leaflet has been studied carefully and und...

Страница 2: ...r full load current of all pumps as they are able to operate at the same time Motor ratings are shown on the set duty plate All non power cable should be limited to 1 5mm All connections must be made using the appropriate wiring drawings for the equipment being installed with particular attention being paid to the supply voltages The supply voltage is shown on the set duty plate Never operate this...

Страница 3: ...to match the pumps fitted If pressure switch settings need altering they should be adjusted as follows Read in conjunction with fig A P1s pump 1 stop pressure which is normally set to 0 5 bar below Pmax pump closed valve head P2s pump 2 stop pressure which is normally set to 1 bar below Pmax when fitted P1 pump 1 differential pressure which is normally set at 1 bar this will start pump one 1 bar b...

Страница 4: ... has been signalled to start it will run for a minimum of 90 seconds default setting even if the demand has cessed The next time the pressure falls the pumps will have been rotated so the opposite pump will be the first to operate If a low level in the break tank occurs all pumps will be stopped until the water supply has been reinstated the pumps will then be automatically released to resume norm...

Страница 5: ...sible Cause Remedy Pump fails to start Power supply failure Control panel fuse blown MCB tripped Low water level Reinstate incoming power supply Replace power supply fuse Reset MCB Reinstate water supply Pump fails to stop Set point set too high System pressure low due to large leak Lower set point Switch unit off until leak is repaired Pump switches on and off quickly Air in system Vessel pre cha...

Страница 6: ...UK Tel 01297 630230 Fax 01297 630270 e mail lowaraukenquiries xyleminc com http www lowara co uk http completewatersystems com Lowara is a trademark of Xylem Inc or one of its subsidiaries 2011 Xylem Inc Lowara reserve the right to make modifications without prior notice cod UKLIT0088 P05 12 Model type Order Code Pump type Serial number Installation date System set point Booster set notes mini f b...