![Xylem LOWARA ESH Series Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/xylem/lowara-esh-series/lowara-esh-series_installation-operation-and-maintenance-manual_892220012.webp)
Cause
Remedy
There is no power
supply.
• Restore the power sup-
ply.
• Make sure all electrical
connections to the pow-
er supply are intact.
The thermal protector
incorporated in the
pump (if any) has trip-
ped.
Wait until the pump has
cooled down. The thermal
protector will automatically
reset.
The thermal relay or
motor protector in the
electric control panel
has tripped.
Reset the thermal protec-
tion.
The protective device
against dry running
has tripped.
Check the:
• liquid level in the tank,
or the mains pressure.
• protective device and its
connecting cables.
The fuses for the
pump or auxiliary cir-
cuits are blown.
Replace the fuses.
7.3 The electric pump starts, but
the thermal protector trips or the
fuses blow immediately after
Cause
Remedy
The power supply ca-
ble is damaged.
Check the cable and re-
place as necessary.
The thermal protection
or fuses are not suited
for the motor current.
Check the components
and replace as necessary.
The electric motor is
short circuit.
Check the components
and replace as necessary.
The motor overloads.
Check the operating condi-
tions of the pump and re-
set the protection.
7.4 The electric pump starts, but
the thermal protector trips or the
fuses blow a short time after
Cause
Remedy
The electrical panel is situ-
ated in an excessively
heated area or is exposed
to direct sunlight.
Protect the electrical
panel from heat source
and direct sunlight.
The power supply voltage
is not within the working
limits of the motor.
Check the operating
conditions of the motor.
A power phase is missing. Check the
• power supply
• electrical connec-
tion
7.5 The electric pump starts, but
the thermal protector trips a varying
time after
Cause
Remedy
There are foreign ob-
jects (solids or fibrous
substances) inside the
pump which have jam-
med the impeller.
Contact the local sales and
service representative.
The pumps delivery
rate is higher than the
limits specified on the
data plate.
Partially close the on-off
valve down stream until the
delivery rate is equal or
less than the limits speci-
fied on the data plate.
The pump is overload-
ed because it is pump-
ing liquid that is too
dense and viscous.
Check the actual power re-
quirements based on the
characteristics of the
pumped liquid and replace
the motor accordingly.
The motor bearings
are worn.
Contact the local sales and
service representative.
7.6 The electric pump starts, but
the system's general protection is
activated
Cause
Remedy
A short circuit in the electri-
cal system.
Check the electrical
system.
7.7 The electric pump starts, but
the system's residual current device
(RCD) is activated
Cause
Remedy
There is an ground
(earth) leakage.
Check the insulation of the
electrical system components.
7.8 The pump runs but delivers too
little or no liquid
Cause
Remedy
There is air inside
the pump or the pip-
ing.
• Bleed the air
The pump is not
correctly primed.
Stop the pump and repeat the
prime procedure.
If the problem continues:
• Check that the mechanical
seal is not leaking.
• Check the suction pipe for
perfect tightness.
• Replace any valves that
are leaking.
The throttling on the
delivery side is too
extensive.
Open the valve.
en - Original instructions
24