Set the parameters for the flowmeter
1. Select the ANALOG INPUT 4 parameter.
2. Select the 4-20 mA FLOW RATE parameter.
3. Set the following values:
Value
Setting
0
4.00 mA
Max
Maximum flow of the 4-20 mA signal from the flowmeter
The default flow values for the MJK 7200 series flowmeters are as follow:
Diameter, in
Flow, gpm
3
800
4
1000
6
3000
8
5000
10
8000
12
10000
18
25000
24
40000
36
100000
48
200000
Set the parameters for the suction pressure transducer
1. Select the ANALOG INPUT 6 parameter.
2. Select the 4-20 mA SUCTION PRESSURE parameter.
3. Set the following values for the applicable transducer:
Value
PXTK30v30
30 inHg to 30 psi
PXTK30v60
30 inHg to 60 psi
PXTK30v100
30 inHg to 100 psi
Vacuum transducer
0
9.26 mA
7.14 mA
6.04 mA
4 mA
Max
30 psi
60 psi
100 psi
14.7 psi
Set the parameters for the discharge pressure transducer
1. Select the ANALOG INPUT 7 parameter.
2. Select the 4-20 mA DISCHARGE PRESSURE parameter.
3. Set the following values:
Value
Setting
0
4.00 mA
Max
Maximum pressure of the discharge pressure transducer in psi
Set the parameters for the fuel level transducer
1. Select the ANALOG INPUT 3 > MURPHY FUEL LEVEL parameter.
2. Press NEXT to return to the main screen.