Position number
Name
Description
Default setting
22
Digital Input 4
Configurable digital input 4, internal pull-
up +24 VDC, contact current 6 mA
Not selected
23
Electronic GND
24
Digital Input 5
Configurable digital input 4, internal pull-
up +24 VDC, contact current 6 mA
Not selected
25
Electronic GND
26
10 VDC power supply
Power 10 VDC, max. 3 mA
-
27
Electronic GND
28
Communication Bus 1
RS485 port 1: RS485-1B N(-)
Multipump
29
RS485 port 1: RS485-1A P(+)
30
RS485 port 1: RS485-COM
31
Communication Bus 2
RS485 port 2: RS485-2B N(-)
Modbus
32
RS485 port 2: RS485-2A P(+)
33
RS485 port 2: RS485-COM
34
Communication Bus 1
RS485 port 1: RS485-1B N(-)
Multipump
35
RS485 port 1: RS485-1A P(+)
36
RS485 port 1: RS485-COM
37
Communication Bus 2
RS485 port 2: RS485-2B N(-)
Modbus
38
RS485 port 2: RS485-2A P(+)
39
RS485 port 2: RS485-COM
40
Relay 1
Configurable relay 1: normally open
Error reporting
41
Configurable relay 1: normally closed
42
Configurable relay 1: common contact
43
Relay 2
Configurable relay 2: normally open
Motor start
44
Configurable relay 2: normally closed
45
Configurable relay 2: common contact
5 Drive operation
Table 2:
1
2
3 4
5
6 7
8
9
Figure 6: Interface screen
NOTICE:
For first-time start-up and programming, the unit is equipped with a start-up genie
to select the appropriate operating mode and other parameters for the intended ap‐
plication.
Table 3:
Position number
Name
Function
1
Display
2
ON/OFF button
• Start and stop the unit
• Reset the errors by pressing for 5 seconds.
For safety and correct product usage, read the manual before this product is used.