![Xylem CentriPro AQUAVAR CPC-FD Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/xylem/centripro-aquavar-cpc-fd/centripro-aquavar-cpc-fd_supplement-manual_891898023.webp)
23
Drive’s Power Connection Terminals (Supplement to Aquavar CPC User’s Manual)
The following tables show maximum wire size and required tightening torque for incomming
power and motor terminals, and grounding terminal lug information.
208…240 Volt, Terminals
208 … 240 Volt
Power Wiring Data
Dis- Ground
HP Type Code
Frame Circuit
connect Motor Lugs
Size Breaker
Switch Terminals NEMA
1 & 12
1 CPC2004xFD R1
2 CPC2007xFD R1 62 in-lbs 7 in-lbs 12 in-lbs
3 CPC2012xFD R1
#4
5 CPC2017xFD R1
35 in-lbs
7.5 CPC2024xFD R2 #8
#6
7 in-lbs
#8
10 CPC2031xFD R2 62 in-lbs
#6
12 in-lbs
18 in-lbs
15 CPC2046xFD
R3
#3
#3
#3
20 CPC2059xFD
R3
62 in-lbs
18 in-lbs
24 in-lbs
25 CPC2075xFD R4 #1/0 #1/0
62 in-lbs
55 in-lbs
#2
30 CPC2088xFD R4
#1/0
#1/0
50 in-lbs
#2/0
70 in-lbs 180 in-lbs
40 CPC2114xFD R4 200 in-lbs
#2/0
200 in-lbs
50 CPC2143xFD
R6
60 CPC2178xFD R6
300 MCM 300 MCM 300 MCM
200 in-lbs 200 in-lbs 354 in-lbs 3 x #3/0
250
in-lbs
75 CPC2221xFD R6
2 x 250
2 x 250
350 MCM
MCM
MCM 354 in-lbs
100 CPC2248xFD R6
275 in-lbs 275 in-lbs
NOTE: “x” represents both NEMA 1 and NEMA 12.