3  Operation

3.1  Note on the packed pump operation

See P2004729, Series e-82 Instruction Manual Chapter 5 for more information.

Tighten the gland nuts

Before you start the pump, back off the packing gland nuts or screws until the gland is loose.
Hand tighten until the gland is snug against the first packing ring. Initially, water might freely

run from the packing. This is normal and should be allowed to continue for a period of time

before you continue to tighten the gland. Tighten the gland nuts slowly and one flat at a time.

Leakage rate

An adequate leakage rate is not one single value for all pumps and installations, but is the

amount required to provide adequate cooling and lubrication. The required leakage is

influenced by operating pressure, fluid temperature, shaft speed, and so forth. For fluid

temperatures in the range of 32°F to 190°F (0°C to 88°C), average leakage rates of 60 to 80

drops per minute are recommended. However, each individual pump and installation has

unique operating conditions that result in widely-variable leakage rate requirements.

Maximum fluid temperature

At fluid operating temperatures near the upper limit of 190°F (88°C), the maximum

temperature rise of the leakage is important. Never operate a packed pump with steam

forming at the gland. This limits the temperature rise to a maximum of about 20°F (-7°C). If

the formation of steam persists at higher leakage rates, you must provide cooling water by

means of an external supply, or a heat exchanger used to cool the bypass flush.

3  Operation

4

Series e-82 Packing Seal Instructions INSTRUCTION MANUAL

Содержание Bell & Gossett e-82 Series

Страница 1: ...INSTRUCTION MANUAL P2005039 Series e 82 Packing Seal Instructions...

Страница 2: ......

Страница 3: ...Product Description 3 2 1 Operation specifications 3 3 Operation 4 3 1 Note on the packed pump operation 4 4 Maintenance 5 4 1 Remove the seal or packing rings 5 4 2 Assemble the packed stuffing box...

Страница 4: ...al injury and damage to property and may void the warranty NOTICE Save this manual for future reference and keep it readily available at the location of the unit 1 2 Safety WARNING The operator must b...

Страница 5: ...e amount of makeup water as well as systems that are subject to a wide variety of chemical conditions and solids buildups Parameter Packing Operating temperature range F C 0 to 200 18 to 93 pH range l...

Страница 6: ...on The required leakage is influenced by operating pressure fluid temperature shaft speed and so forth For fluid temperatures in the range of 32 F to 190 F 0 C to 88 C average leakage rates of 60 to 8...

Страница 7: ...Impeller key 7 Volute capscrew 8 Impeller washer 9 Impeller 10 Impeller capscrew 11 Volute 12 Impeller lockwasher 13 Volute gasket 14 Coverplate 15 Drip drain 16 Lantern ring 17 Packing 18 Gland bolt...

Страница 8: ...See the note on the packed pump operation in the Operation chapter for more information 4 Maintenance 6 Series e 82 Packing Seal Instructions INSTRUCTION MANUAL...

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ...ed analytics solutions for water electric and gas utilities In more than 150 countries we have strong long standing relationships with customers who know us for our powerful combination of leading pro...

Отзывы: