
5 Operation
5.1 Sequence of operation:
1. When the “Stop” and “Lead” float contact closes, the pump will energize and the “Pump
Run” light will illuminate. The pump will remain operational until the “Stop” float opens.
2. If the level continues to rise, the “High” float will alarm. This will illuminate the 360 -
degree visible beacon and buzzer will sound 85 decibels at 10’.
5.2 Remote monitoring dry contacts:
Normally Open dry contacts for high level, Pump run, and Pump fault.
Note: Refer to wiring schematic for proper termination.
5 Operation
10
4DWC Three Phase Simplex Control Panel Instruction Manual
Содержание Bell & Gossett 4DWC
Страница 1: ...Instruction Manual IM407 4DWC Three Phase Simplex Control Panel...
Страница 2: ......