35
Version 1 – GBR (25/10/2022)
D-502-0287
5.4.3.
Description of the ventilation power setting range
-
Unit output settings
5.4.4.
Ventilation Output Settings
1.
In the regular regime, double-click on button 1 or 2 or 3 to enter the settings regime – LED 10 flashes
(fan pictogram).
2.
As long as LED 10 flashes (approx. 4 s), set the required degree of ventilation according to Table 19
or according to your request with buttons 1 or 3: If necessary, consult an HVAC professional for the
correct ventilation performance setting.
o
If you did not manage to complete the settings (LED 10 stopped flashing), repeat the procedure.
After setting the request, the newly set value is automatically saved (approx. within 4 s) and the controller
switches to the regular regime.
5.4.5.
Display of the LED Indicated Statuses on the Controller
-
The LED signalling on the controller is the same for all the unit types.
Tab. 16
Tab. 15
Fig. 42