background image

Xtreme Power Conversion Corporation

TX90 6kVA & 10kVA Service Manual

Page 31

Uninterruptible Power Supply

 

•  Fill the output voltage measured by the power meter to Calibration Step2, then click ”Calibration2” icon.

•  Press Calibration 2 icon after the figure is filled, then buzzer will beep twice to show the calibration is 

complete.

•  After calibration, the output voltage will be changed and remained for approx. 4 seconds. Please quickly 

check with Power meter if the output voltage shown as below:

•  The output voltage shall be 220.7 +/-0.3V (220.4V~221.0V) if no transformer is installed.

•  Otherwise, please refer to the followings if there is a transformer installed.

Setting calibration parameter

Output Voltage Range

I/P 

→ 

Else system, O/P 

→ 

240V system

225.0 +/-0.3V (224.7V~225.3V)

I/P 

→ 

Else system, O/P 

→ 

120V system

112.5 +/-0.3V (112.2V~112.8V)

I/P 

→ 

208V system, O/P 

→ 

208V system

225.0 +/-0.3V (224.7V~225.3V)

I/P 

→ 

208V system, O/P 

→ 

120V system

129.8 +/-0.3V (129.5V~131.1V)

Caution:

•  You are suggested to connect with 80% to 100% load in order to make sure the tolerance of the calibrated 

values will be smaller and the values will be more accurate.  All values will be calibrated except the value 

of load% if the output load of UPS are less than 30% when you proceed calibrated action.

•  Make sure the tolerance of the adjustable range will be less than 8% for Voltage and 15% for Load; other-

wise, the setting will be in failure and the error code will be shown in the LCD panel.

•  The UPS will escape from calibration mode if the setting is not complete in 10 min. after the UPS is in the 

calibration mode.

•  The values of both “load%” and “output voltage” must be round to Integer.

•  The input voltage in the Calibration 2 shall be accurate; therefore, make sure you will round the value 

to 1st decimal place.

The Wiring Diagram of the Transformer (The red lines indicated below are for the connections of the no load in 

calibration.)

Содержание TX90 6kVA

Страница 1: ...TX90 6kVA 10kVA Online UPS 6kVA 10kVA Models Service Manual www xpcc com 2017 Xtreme Power Conversion Corporation All rights reserved ...

Страница 2: ...l Mode 13 Check Measured Values and Figures Detected by the UPS 15 Viewing the UPS Default Settings 17 Changing the UPS Default Settings 19 System Block Diagram and PCB Wiring Diagram 21 SystemBlockDiagram 21 Unit Wiring Diagram 22 Unit Test Calibration Setting Explanation 25 VRFunction Explanation 25 ElectricalCharacteristics 25 Startup Procedure for Debug UPS 26 UPS Inverter Output Balance Check...

Страница 3: ...Code Er05 42 Error Code Er06 43 Error Code EPO 44 Error Code Er08 45 Error Code Er09 46 Error Code Er10 47 Error Code Er11 48 Error Code Er12 49 Error Code Er13 50 Error Code Er14 51 Error Code Er15 52 Error Code Er16 53 Error Code Er17 54 Error Code Er18 55 Error Code Er20 56 Error Code Er21 57 Error Code Er22 58 Error Code Er23 59 Error Code Er24 60 Error Code Er26 61 Error Code Er27 62 Error Co...

Страница 4: ... Error Code Er31 66 Error Code Er32 67 Error Code Er33 68 Error Code Er34 69 Calibration Error Code CEr1 70 Calibration Error Code CEr2 71 Calibration Error Code CEr3 72 Calibration Error Code CEr4 73 Calibration Error Code CEr5 74 Calibration Error Code CEr6 75 Appendix A 76 PCB Installation Position 76 PCB Placement 78 ...

Страница 5: ...aded 5 UPS Working in specified mode 6 A Blackout Transfer occurred in UPS Output 7 Bypass Input Abnormal UPS fails to transfer to bypass Bypass Abnormal at ECO mode 8 Utility Input Abnormal 9 OFF UPS Shut off 10 LINE OFF UPS Abnormal Lock 11 UPS Flow Display 12 4 Digit Measurement Display 13 Indicates the item to be measured 14 UPS ON Switch or Alarm Silence 15 UPS OFF Switch 16 Previous Page or ...

Страница 6: ... means AC SCR Driver on or Battery SCR Driver On 30 Sr05 3rd Soft Start Boosts BUS up to desired voltage 31 Sr06 Inverter Soft Start to reach to the desired output voltage of Inverter The below Error Codes indicate you the error status of the UPS 1 Er01 1st stage DC BUS capacitor pre charge abnormal after 50 sec onds or Battery Fuse fails 2 Er02 AC SCR or Battery SCR soft Start abnormal after 2 se...

Страница 7: ... each other 32 Er32 Sync Signal Error 33 Er33 Isolated transformer overheat 34 Er34 Balance function conflict 35 ER35 Output Parallel Failed 36 CEr1 Utility voltage out of range 37 CEr2 Bypass Voltage out of range 38 CEr3 Inverter Voltage out of range 39 CEr4 Load Percentage out of range 40 CEr5 Battery Voltage out of range 41 CEr6 UPS Output Voltage out of range Remarks 1 When one of the Er06 EPO...

Страница 8: ...ow Flashing green LED indicates that the utility input voltage is outside the acceptable window 4 Green LED indicates that Bypass Input is normal 5 UPS ON Alarm Silence 6 Go to previous page or change the setting of the UPS 7 Confirm a changed setting 8 Go to the next page 9 UPS OFF Switch 10 Special functions log in out 11 UPS is working under ECO Economy mode 12 UPS Fault or Abnormal Rear Panel ...

Страница 9: ... may use optional interface cards for Relay Dry Contact and SNMP These cards may be used simultaneously The software bundled with the UPS is compatible with many operating systems such as Windows 98 2000 ME NT and XP For other applications such as Novell NetWare Unix or Linux please contact your local distributor for a proper solution When the optional interface cards are used together with the on...

Страница 10: ...n Position Install the UPS in a proper environment to minimize the possibility of damage to the UPS and to extend the life of the UPS Please follow these requirements 1 Keep at least 12 inches clearance from the rear panel of the UPS to the wall 2 Keep at least 8 inches clearance from the rear panel of the External Battery Pack EBP to the wall Refer to the T90 EBP920 EBP940 EBP960 user manual for ...

Страница 11: ...s configured at 208V but the actual input is 240V then the output voltages will boost up 15 Input Configuration 208V input applications 208V input with a 120 240V output is the default for these systems This means the in verter output is programmed to 208V and the output transformer primary tap is set to the 208V setting These are the default settings for this system Please refer to output Option ...

Страница 12: ...acity output Please note the jumpers between G2 N22 N22 N21 and L22 L21 for this option See below For any other output configurations needed please contact Xtreme Power Tech Support Please refer to the specifications of input current output current and recommended conductors listed below a AC input and output minimum 75 C copper wire Model Maximum Input Current Input Breaker Size Input Output Cond...

Страница 13: ... Utility and Bypass inputs are normal UPS will display first figure A1 and then figure B A1 B The UPS is now in Bypass Mode It will proceed to self test automatically If no abnormal message appears then the pre startup of the UPS was successful and the charger begins to charge the batteries Press the UPS On switch for approximately three seconds The Buzzer sounds twice and the LCD display changes ...

Страница 14: ... be protected Start up in Battery Mode Cold Start Make sure the UPS has at least one string 20 pcs of batteries Push the UPS On switch once for approximately 5 seconds to wake the UPS The buzzer will sound twice The LCD display will change from figure A to figure G for approximately 15 seconds Press the UPS On switch again for about three seconds until the LCD display changes from figure G to figu...

Страница 15: ...res detected by the UPS use the scroll up and scroll down keys When you scroll down the LCD will display figure C Voltage from Utility Input figure I1 Voltage from Bypass Input figure J Frequency from Utility Input figure K Frequency from Bypass Input figure L UPS Output Voltage figure M UPS Output Frequency figure N UPS Output Load figure O UPS Battery Voltage figure P UPS Inner Temperature I1 Vo...

Страница 16: ...ower Conversion Corporation TX90 6kVA 10kVA Service Manual Page 16 Uninterruptible Power Supply K Frequency of Bypass Input L UPS output voltage M UPS output frequency N UPS output load level O Battery voltage ...

Страница 17: ... will display in sequence figure Q1 buzzer figure R Self test figure S Bypass Voltage Windows figure T Output Frequency Synchronization Window figure U Inverter Output Voltage figure V UPS Operation Mode figure W Output Volt age Micro Tune Value figure X UPS Id figure Y Parallel function status Buzzer and Self test can only be changed in this mode while the UPS is on All other settings must be cha...

Страница 18: ...electable to 1Hz U Inverter output voltage set to 208V Selectable to 200 208 220 230 240V This is the voltage sent to the output transformer primary The UPS output voltages depend on what output con figuration is chosen Please refer to the Output Configuration section of this manual V The UPS is operating in normal mode Selectable to ECO CF50 CF60 and Normal W Output Voltage Adjustment 1 2 3 0 1 2...

Страница 19: ...indicates the bypass frequency window of the Inverter Output The acceptable setting values are 3 Hz and 1 Hz Figure U indicates the acceptable Inverter Output Voltage Possible values are 200 208 220 230 or 240 VAC The inverter output voltage needs to match the input voltage for this system Figure V indicates the operation modes of the UPS Possible values are Online Eco Economy mode fixed 50 Hz Out...

Страница 20: ...oblem For further help consult your local distributor 3 Press the Off key for five seconds A buzzer will sound twice 4 Turn Off the Utility Input breaker 5 Even if the UPS lock problem is solved now consult with your local distributor to make sure that the error condition is resolved Shut Off 1 Press the Off key for five seconds The Inverter output will be turned off and the output load will be su...

Страница 21: ...t Breaker to protect the UPS Bypass circuit from over current e EMI Filter on UPS Utility Input to eliminate the magnetic interference from AC Source or UPS Utility Input f EMI Filter on UPS Bypass Input to eliminate the magnetic interference from AC Source or UPS Bypass Input g Fuse for UPS Utility Input to provide over current protection for UPS Rectifier Circuit h Rectifier and Booster When Uti...

Страница 22: ...ct Board RS485 card USB card 2nd RS232 card etc w Remote Control Box To provide remote monitoring and control functions Unit Wiring Diagram MSII series PCB boards Please find the description as below Item Description Part No Function 1 Control MSDI0XX To generate all control signals and also AC DC detecting signals 2 Power Driver MSDD0XX AC DC DC DC AC AC and circuit working power supply MSED0XX M...

Страница 23: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 23 Uninterruptible Power Supply Unit Wiring Diagram of TX90 T90 6K ...

Страница 24: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 24 Uninterruptible Power Supply Unit Wiring Diagram of TX90 T90 10K ...

Страница 25: ...VR Function Explanation PCB Number Function Location MSDC0XX Adjust Charger Output Voltage VR1 CHEC0XX Adjust Charger Output Voltage VR1 Electrical Characteristics Battery Charging Voltage 25 C Model Battery Charging Voltage TX90 T90 6kVA 10kVA 273 0Vdc Battery Low Warning and Battery Cut off Overload time out versus Inverter mode and Bypass mode ...

Страница 26: ...charger is charging the BUS then buzzer will beep once Push key pad for a second till buzzer beeps twice The LCD displays from Sr03 to Sr04 then the UPS proceeds the 2nd stage soft start which means battery SCR is turned on to charge the BUS then the buzzer will beep once Push key pad for a second till buzzer beeps twice The LCD displays from Sr04 to Sr05 then UPS pro ceeds the 3rd stage soft star...

Страница 27: ...heck Connect the UPS as shown below Disconnect the isolation transformer if any otherwise it is not possible to measure whether the UPS out put waveform is in balance or not Connect a 220Vac 50 60 Hz to the UPS to start up the UPS and make sure it is on Line Mode Without output load connected please connect a fixture in parallel The fixture is made with 1M ohms re sistors and 1uF 63V capacitor in ...

Страница 28: ... continuously it means your setting is in failure Calibration It is divided into two parts one is front panel calibration and the other is PC calibration Notice The calibration with load connected doesn t include the power loss of the galvanic isolation transformer therefore the load can only be connected behind the output filter as indicated as A B the UPS with galvanic isolation transformer or t...

Страница 29: ...0 Battery Voltage 273 0Vdc The UPS will escape from the calibration mode if the calibration is not finished in 10 minutes and go to shutdown automatically and show Line OFF on LCD panel Tuning the values shown on the LCD display are the same as that on the meter then you may go to next Calibration item The load on LCD panel means the higher value of VA or W therefore you are recommended to use Re ...

Страница 30: ...lick Calibration1 icon If the buzzer beeps intermittently and continuously it means your calibration is in failure You may click skip step 2 icon and repeat If the buzzer beeps twice it means the Calibration Step 1 is done successfully then you may enter into Calibration Step 2 The ECO LED light up to indicate the UPS is working under the Calibration Step2 Remove the load to Null status then remov...

Страница 31: ... O P 208V system 225 0 0 3V 224 7V 225 3V I P 208V system O P 120V system 129 8 0 3V 129 5V 131 1V Caution You are suggested to connect with 80 to 100 load in order to make sure the tolerance of the calibrated values will be smaller and the values will be more accurate All values will be calibrated except the value of load if the output load of UPS are less than 30 when you proceed calibrated acti...

Страница 32: ... P Voltage Else system O P Voltage 220V system The turns ratio of Primary and Secondary of the transformer is 1 to 1 Input Coil 0V 240V Output Coil 0V 120V Calibration2 Block I P Voltage Else system O P Voltage 120V system The turns ratio of primary and secondary of the transformer is 2 to 1 Input Coil 0V 208V Output Coil 0V 208V Calibration2 Block I P Voltage 208V system O P Voltage 208V system ...

Страница 33: ...2 Block I P Voltage 208 system O P Voltage 120V system The turns ratio Primary and Secondary of the transfomer is 208 to 120 Frequency Converter CVCF Mode Setting Notice The UPS can be set as Frequency Converter CVCF mode If the UPS is Dual Input Model you have to make sure the Bypass Input Breaker is set at OFF position on the contrary if the UPS is Single Input Model you have to remove the power...

Страница 34: ...n function will be activated after 6 25 VDC is applied between pin 9 and pin 10 for 5 sec onds The capacity of each relay contact is 40 VDC 25mA Installation Position slot 1 CHA CN7 or slot 2 CHB CN8 Flexible signal output for N C Normal close or N O Normal open contact by shorting pins 1 2 or pins 2 3 from JP1 5 The shutdown function will be enabled 1 minute after blackout occurs if pins 1 2 of b...

Страница 35: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 35 Uninterruptible Power Supply Interface Card Installation 1 3 2 ...

Страница 36: ...d by qualified personnel only 1 Unscrew the bottom of the front panel as indicated in Step 1 below 2 Remove the front panel as indicated in Step 2 TX90 6K shown above 3 Remove the screw of the battery pack fastener as shown in Step 3 4 Remove the fastener as shown in Step 4 5 Unplug the hot swappable battery connectors as shown in Step 5 ...

Страница 37: ... Conversion Corporation TX90 6kVA 10kVA Service Manual Page 37 Uninterruptible Power Supply 6 Rotate the battery pack handle 90 degrees as shown in Step 6 7 Remove the battery packs from the UPS as shown in Step 7 ...

Страница 38: ...how an error code as indicated at Chapter 1 Please follow the troubleshooting indicated below Error Code Er01 Definition The UPS is in the 1st stage soft start procedure but the DC bus voltage can not reach 50Vdc within 5 seconds or can not reach anticipative charging voltage about either present 80 of battery voltage or present output voltage of charger within 30 seconds Flow Chart ...

Страница 39: ...ower Supply Error Code Er02 Definition The UPS is in 2nd stage soft start procedure but the DC Bus can not reach and maintain anticipative charging voltage after 2 seconds approx present 85 of peak voltage of utility either present 80 of battery volt age or output voltage of charger Flow Chart ...

Страница 40: ...X90 6kVA 10kVA Service Manual Page 40 Uninterruptible Power Supply Error Code Er03 Definition The UPS is in 3rd stage soft start procedure but the DC bus voltage can not reach to anticipative charg ing voltage within 30 seconds Flow Chart ...

Страница 41: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 41 Uninterruptible Power Supply Error Code Er04 Definition It means the UPS Inverter Output is Abnormal Flow Chart ...

Страница 42: ...reme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 42 Uninterruptible Power Supply Error Code Er05 Definition It means the battery is weak or bad after self test is executed Flow Chart ...

Страница 43: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 43 Uninterruptible Power Supply Error Code Er06 Definition It means the UPS is protected from short circuited Flow Chart ...

Страница 44: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 44 Uninterruptible Power Supply Error Code EPO Definition It means the UPS enters into EPO Emerge Power Off mode Flow Chart ...

Страница 45: ...treme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 45 Uninterruptible Power Supply Error Code Er08 Definition It means the DC Bus of the UPS is protected from over voltage Flow Chart ...

Страница 46: ...treme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 46 Uninterruptible Power Supply Error Code Er09 Definition It means the DC Bus of the UPS is protected from under voltage Flow Chart ...

Страница 47: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 47 Uninterruptible Power Supply Error Code Er10 Definition It means the UPS Inverter is protected from over current Flow Chart ...

Страница 48: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 48 Uninterruptible Power Supply Error Code Er11 Definition It means the UPS is protected from over heat Flow Chart ...

Страница 49: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 49 Uninterruptible Power Supply Error Code Er12 Definition It means the UPS inverter is protected from overloaded Flow Chart ...

Страница 50: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 50 Uninterruptible Power Supply Error Code Er13 Definition It means the charger is out of order Flow Chart ...

Страница 51: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 51 Uninterruptible Power Supply Error Code Er14 Definition It means the fan of the UPS is abnormal Flow Chart ...

Страница 52: ...6kVA 10kVA Service Manual Page 52 Uninterruptible Power Supply Error Code Er15 Definition It means Maintenance Bypass Switch CAM Switch is not used properly or the Maintenance Bypass Switch is activated when the UPS is in CVCF mode Flow Chart ...

Страница 53: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 53 Uninterruptible Power Supply Error Code Er16 Definition It means the output parameter set error in parallel system Flow Chart ...

Страница 54: ...nversion Corporation TX90 6kVA 10kVA Service Manual Page 54 Uninterruptible Power Supply Error Code Er17 Definition It means the ID number is in conflict in parallel system or ID number error in single unit Flow Chart ...

Страница 55: ...orporation TX90 6kVA 10kVA Service Manual Page 55 Uninterruptible Power Supply Error Code Er18 Definition It means the data inside of the EEPROM on the control board is abnormal and the data is set as default values Flow Chart ...

Страница 56: ...e Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 56 Uninterruptible Power Supply Error Code Er20 Definition It means the capacitor in the DC Bus of the UPS can not be discharged Flow Chart ...

Страница 57: ... Conversion Corporation TX90 6kVA 10kVA Service Manual Page 57 Uninterruptible Power Supply Error Code Er21 Definition It means the communication error in parallel system or can t find the UPS which ID 1 Flow Chart ...

Страница 58: ...eme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 58 Uninterruptible Power Supply Error Code Er22 Definition It means the SCR in UPS bypass loop or the output fuse is abnormal Flow Chart ...

Страница 59: ...wer Conversion Corporation TX90 6kVA 10kVA Service Manual Page 59 Uninterruptible Power Supply Error Code Er23 Definition It means the SCR Relay of the UPS in Inverter loop or output fuse is abnormal Flow Chart ...

Страница 60: ...wer Conversion Corporation TX90 6kVA 10kVA Service Manual Page 60 Uninterruptible Power Supply Error Code Er24 Definition It means there is voltage in bypass loop when the UPS is operated in CVCF mode Flow Chart ...

Страница 61: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 61 Uninterruptible Power Supply Error Code Er26 Definition It means the PFC of the UPS is protected from over current Flow Chart ...

Страница 62: ...eme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 62 Uninterruptible Power Supply Error Code Er27 Definition It means the UPS isn t operated in normal mode in parallel system Flow Chart ...

Страница 63: ...onversion Corporation TX90 6kVA 10kVA Service Manual Page 63 Uninterruptible Power Supply Error Code Er28 Definition It means when the UPS is operated in bypass mode there is an overload time out occurred Flow Chart ...

Страница 64: ...wer Conversion Corporation TX90 6kVA 10kVA Service Manual Page 64 Uninterruptible Power Supply Error Code Er29 Definition It means the charger voltage is higher than 300Vdc and the charger is been off Flow Chart ...

Страница 65: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 65 Uninterruptible Power Supply Error Code Er30 Definition It means the inverter balance error over than 30 seconds Flow Chart ...

Страница 66: ...wer Conversion Corporation TX90 6kVA 10kVA Service Manual Page 66 Uninterruptible Power Supply Error Code Er31 Definition It means the capacity of driver board is less than control board setting value Flow Chart ...

Страница 67: ...r Conversion Corporation TX90 6kVA 10kVA Service Manual Page 67 Uninterruptible Power Supply Error Code Er32 Definition It means the signal of sync error occurred in communication for parallel function Flow Chart ...

Страница 68: ... Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 68 Uninterruptible Power Supply Error Code Er33 Definition It means the isolated transformer of the UPS is protected from over heat Flow Chart ...

Страница 69: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 69 Uninterruptible Power Supply Error Code Er34 Definition It means the balance function conflict in parallel system Flow Chart ...

Страница 70: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 70 Uninterruptible Power Supply Error Code Er35 Definition It means output parallel failed Flow Chart ...

Страница 71: ...r Conversion Corporation TX90 6kVA 10kVA Service Manual Page 71 Uninterruptible Power Supply Calibration Error Code CEr1 Definition It means the input voltage of the UPS is excessive of adjustable range Flow Chart ...

Страница 72: ... Conversion Corporation TX90 6kVA 10kVA Service Manual Page 72 Uninterruptible Power Supply Calibration Error Code CEr2 Definition It means the bypass input voltage of the UPS is out of adjustable range Flow Chart ...

Страница 73: ...Conversion Corporation TX90 6kVA 10kVA Service Manual Page 73 Uninterruptible Power Supply Calibration Error Code CEr3 Definition It means the Inverter Output Voltage of the UPS is out of adjustable range Flow Chart ...

Страница 74: ...er Conversion Corporation TX90 6kVA 10kVA Service Manual Page 74 Uninterruptible Power Supply Calibration Error Code CEr4 Definition It means the output load level of the UPS is out of adjustable range Flow Chart ...

Страница 75: ...wer Conversion Corporation TX90 6kVA 10kVA Service Manual Page 75 Uninterruptible Power Supply Calibration Error Code CEr5 Definition It means the battery voltage of the UPS is out of adjustable range Flow Chart ...

Страница 76: ...wer Conversion Corporation TX90 6kVA 10kVA Service Manual Page 76 Uninterruptible Power Supply Calibration Error Code CEr6 Definition It means the output voltage of the UPS is out of adjustable range Flow Chart ...

Страница 77: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 77 Uninterruptible Power Supply Appendix A PCB Installation Position The PCB of TX90 T90 6K Installation Position ...

Страница 78: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 78 Uninterruptible Power Supply The PCB of TX90 T90 10K Installation Position ...

Страница 79: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 79 Uninterruptible Power Supply PCB Placement MSDI0XX PCB ...

Страница 80: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 80 Uninterruptible Power Supply MSDD0XX PCB ...

Страница 81: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 81 Uninterruptible Power Supply MSED0XX PCB ...

Страница 82: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 82 Uninterruptible Power Supply MSEDSXX PCB ...

Страница 83: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 83 Uninterruptible Power Supply MSDC0XX PCB ...

Страница 84: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 84 Uninterruptible Power Supply MSDM0XX PCB MSDM3XX PCB ...

Страница 85: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 85 Uninterruptible Power Supply MSDF0XX PCB ...

Страница 86: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 86 Uninterruptible Power Supply MSEF0XX PCB ...

Страница 87: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 87 Uninterruptible Power Supply MSDF4XX PCB ...

Страница 88: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 88 Uninterruptible Power Supply MSEF4XX PCB ...

Страница 89: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 89 Uninterruptible Power Supply MSEFSXXPCB ...

Страница 90: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 90 Uninterruptible Power Supply MSEB0XX PCB MSEZ2XX PCB ...

Страница 91: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 91 Uninterruptible Power Supply MSEK0XX PCB MSXN0XX PCB ...

Страница 92: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 92 Uninterruptible Power Supply MSFD6XX ...

Страница 93: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 93 Uninterruptible Power Supply MSFD5XX ...

Страница 94: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 94 Uninterruptible Power Supply MSFB0XX MSFD4XX ...

Страница 95: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 95 Uninterruptible Power Supply MSFD7XX MSFZ0XX MSFE4XX ...

Страница 96: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 96 Uninterruptible Power Supply MSFL0XX ...

Страница 97: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 97 Uninterruptible Power Supply MSFF5XX ...

Страница 98: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 98 Uninterruptible Power Supply MSFF3XX ...

Страница 99: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 99 Uninterruptible Power Supply MSFZ1XX ...

Страница 100: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 100 Uninterruptible Power Supply CHECOXX ...

Страница 101: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA Service Manual Page 101 Uninterruptible Power Supply CHECOXX ...

Отзывы: