Xtreme Power Conversion Corporation
M90U-80 & 140 User’s Manual
Page 21
Uninterruptible Power Supply
Table 2.10.1
Model
15KVA
20KVA
30KVA
40KVA
45KVA
60KVA
75KVA
Current (A)
45
60.1
90
120.2
135
180.3
225
Power cable (mm2)
16
16
50
50
95
95
150
Fixation torque force (lb-
in)
88.3
88.3
88.3
88.3
88.3
88.3
88.3
Model
80KVA
90KVA
100KVA
105KVA
120KVA
140KVA
Current (A)
240.4
270
300.5
315
360.6
420.7
Power cable (mm2)
150
240
240
95 x 2
95 x 2
120 x 2
Fixation torque force (lb-
in)
88.3
100
100
100
100
100
Power cable size based on THHN 90° copper wire
Notice: Installer has to consider the max. current and wiring gauge when considering future extension.
Warning:
1. When Load is less than 20KVA, at least one layers of battery modules (4 modules) have to be installed.
2. When Load is between 20KVA and 40KVA, at least two layers of battery modules (8 modules) have to be in
-
stalled.
3. When Load is between 40KVA and 60KVA, at least three four of battery modules (12 modules) have to be
installed.
4. When Load is between 60KVA and 80KVA, at least four of battery modules (16 modules) have to be installed.
5. The same type of battery has to be used, if the battery is in parallel application.
Table 2.10.2
Model
15KVA
20KVA
30KVA
40KVA
45KVA
60KVA
75KVA
Current (A)
73.5
98
147
196
220.5
294
367.2
Power cable (mm2)
25
25
95
95
150
150
240
Fixation torque force
(lb-in)
100
100
100
100
100
100
100
Model
80KVA
90KVA
100KVA
105KVA
120KVA
140KVA
Current (A)
392
441
490
514.5
588
686
Power cable (mm2)
240
120 x 2
120 x 2
150 x 2
150 x 2
185 x 2
Fixation torque force
(lb-in)
100
100
100
100
100
100
Power cable size based on THHN 90° copper wire