TROUBLESHOOTING
Note:
The
Audible
Alarm
can
be
silenced
by
pressing
any
one
of
the
three
buttons
on
the
front
of
the
UPS,
except
when
a
low
‐
battery
condition
exists.
The
audible
alarm
can
also
be
permanently
disabled
in
the
configuration
section.
Displayed
on
LCD
Audible
Alarm
Alarm
Description
What
You
Should
Do
Output
Overload
Two
Beeps
per
second
The
UPS
is
overloaded
(in
Line
Mode).
Your
equipment
needs
more
power
than
the
UPS
can
provide.
The
UPS
operates
in
bypass.
Shut
off
the
least
important
equipment
connected
to
the
UPS.
If
this
solves
the
overload
problem,
the
UPS
will
switch
from
bypass
back
to
normal
operation.
Battery
Test
No
Beeps
The
UPS
is
doing
a
battery
test.
No
action
needed.
The
UPS
will
return
to
normal
operation
when
it
successfully
completes
the
battery
test.
Over
‐
Charge
Constant
beep
Batteries
are
overcharged.
Turn
off
protected
loads.
Turn
off
UPS
and
call
your
local
dealer
Low
Battery
2
beeps
every
5seconds
The
unit
is
operating
on
Battery
Power
and
will
shut
down
soon
due
to
very
low
battery
voltage.
The
ON
Battery
LED
will
also
flash
The
unit
will
restart
Automatically
when
acceptable
power
returns.
On
‐
Battery
Once
every
5
seconds
The
unit
is
operating
on
Battery
Power.
Save
your
data
and
perform
a
controlled
shutdown.
Charger
Failure
Constant
beep
Charger
has
failed.
Phone
the
local
dealer
Over
‐
Temperature
Constant
beep
High
ambient
Temperature.
If
the
internal
temperature
is
higher
than
55C,
the
UPS
will
shutdown.
Allow
the
UPS
to
cool.
Make
sure
the
unit’s
fans
and
vent
holes
are
not
blocked.
Make
sure
the
ambient
surrounding
temperature
is
not
above
40
degree
C.
If
these
actions
do
not
solve
the
problem,
call
your
service
representative.
Output
Short
Constant
beep
Output
short
circuit
Call
the
Local
dealer
High
output
Voltage
Constant
beep
High
output
voltage
Call
the
Local
dealer
Low
Output
Voltage
Constant
beep
Low
output
voltage
Call
the
Local
dealer
Bus
Fault
2
Beeps
per
second
High
internal
DC
bus
Voltage.
Turn
off
protected
loads.
Turn
off
UPS
and
call
your
local
dealer
Site
wiring
Fault
1
Beep
per
second
Voltage
detected
Between
Neutral
and
Ground
UPS
mains
connector
polarity
Wrong.
Rotate
the
connector
(Schuko).
UPS
installed
to
mains
supply
without
ground.
Line
abnormal
1
Beep
per
second
Wrong
AC
Line
backed
up
during
auto
restart