Uninterruptible Power Supply
Communication protocol setting
Display setting
Figure 7.1 Hyper terminal setting
2. After you finished the setting, you can type the command in the comma nd area.
3. +BUS voltage regulation: Type “BUSP+/- XX” command (XX is two digits from 00 to 19), then
press the “ENTER” key, +BUS voltage will rise (drop) a little step.
4. -BUS voltage regulation: Type “BUSN+/- XX” command (XX is two digits from 00 to 19), then press the
“ENTER” key, -BUS voltage will rise (drop) a little step.
5. INV output voltage regulation: Type “V+/- X” command (X is a digit from 0 to 6), then press the
“ENTER” key, output voltage will rise (drop) a little step.
6. INV output voltage setting: Type “VXXX” command (XXX is 208/220/230/240), then press the
“ENTER” key, INV output voltage will be set to 208V/220V/230V/240V.
7. charger current setting: CHGC XX” command (XX is from 0 to 4 ), then press the
“ENTER” key, Charger current will be set to 1A~4A
Regulation Process for Single UPS:
1. BUS voltage regulation: When the UPS runs into AC mode, measure ±BUS voltage with the
multimeter, and then regulate the ±BUS voltages to 370±0.5V by using BUS regulation command.
(BUS voltage can be regulated about 0.5V every point by using BUS regulation command).
2. INV output voltage regulation: When the UPS runs in the Inverter mode, measure the output
voltage withthe multimeter, then regulate the output voltage to 230±0.5V by using output voltage
regulation command. (INV output voltage can be regulated about 0.8V every point by using output
voltage regulation command).