background image

Xtralis Pty Ltd

XCC Product Guide

www.xtralis.com

5

2

Pipe Networks

Note:

To achieve EN 54-20 Class C compliance you must use the pre-engineered pipe networks
described in this section.

These pre-engineered pipe networks provide installations which have a sensitivity better than 8%
obscuration/m and transport time better than 90 sec. This ensures that they have a good margin of
performance as a Class C detector and allow hole positions along the pipe to be varied from exact equal
spacing while still achieving an acceptable system balance.

Wherever possible the hole sizes have been restricted to increments of 0.5mm and a maximum of two hole
sizes on any one detector (e.g. 3mm holes with last hole 3.5mm). However, this is not always possible,
particularly on the designs using capillary sampling. For these, more than two drills sizes are often needed on
a particular design to accommodate the flexibility given for the length of capillary pipes – being from 0.25m to
4m long (Note: capillaries should be equal lengths for a particular detector).

Fire-Alarm Threshold Settings:

There are 4 sensitivity thresholds provided on the XCC detector to accommodate different numbers of holes,
pipe lengths and pipe arrangements. These are denoted I, II, III and IV (with I being the most sensitive).

Pre-Alarm Threshold Settings:

The Pre-alarm condition on the XCC detector is signaled at 70% of Fire-Alarm Threshold Settings.

The tables in the following sections define the pre-engineered systems allowed.

Refer to Figure 2-1 and Figure 2-2 below for examples of single pipe and single branch (U-style) pipe
networks.

Figure 2-1: Single pipe network

Figure 2-2: Branch Pipe network

Содержание XCC-010

Страница 1: ...Xtralis Class C XCC Product Guide XCC 010 XCC 01000 MRN May 2011 D N 14159_07 P N 29185 ...

Страница 2: ......

Страница 3: ...ment damage Xtralis is not responsible and cannot be held accountable for any liability that may arise due to improper use of the equipment and or failure to take proper precautions Only persons trained through an Xtralis accredited training course can install test and maintain the system Liability You agree to install configure and use the products strictly in accordance with the User Manual and ...

Страница 4: ...iption Caution This icon is used to indicate that there is a danger to equipment The danger could be loss of data physical damage or permanent corruption of configuration details Warning This icon is used to indicate that there is a danger of electric shock This may lead to death or permanent injury Warning This icon is used to indicate that there is a danger of inhaling dangerous substances This ...

Страница 5: ...eceiving antenna increase the separation between the equipment and receiver connect the equipment to a power outlet which is on a different power circuit to the receiver or consult the dealer or an experienced radio television technician for help FDA This Xtralis product incorporates a laser device and is classified as a Class 1 laser product that complies with FDA regulations 21 CFR 1040 10 The l...

Страница 6: ...XCC Product Guide Xtralis Pty Ltd iv www xtralis com This page is intentionally left blank ...

Страница 7: ... a Fire Panel with an EOL Resistor 11 3 7 Wiring to an Addressable Loop Module 11 3 8 Power Source 12 4 Installation 13 4 1 Mounting the Detector 13 4 2 Connection to Pipe Network 14 4 3 Battery Backup 15 4 4 Startup 15 4 5 Commissioning 16 4 6 Installation Checklist 17 5 Operation 19 5 1 Display 19 6 Maintenance and Servicing 21 6 1 Internal Components 21 6 2 Opening and Closing the Detector 22 6...

Страница 8: ...XCC Product Guide Xtralis Pty Ltd 2 www xtralis com This page is intentionally left blank ...

Страница 9: ...outputs This Product Guide provides you with comprehensive knowledge of the detector It includes instructions on installing cabling and powering up the XCC detector It also provides information on the features technical specifications and an understanding of the components and their function This guide is for anyone involved with the design maintenance and purchasing of a system that includes the ...

Страница 10: ...010 detector can cover an area of up to 800 m 8000 sq ft l Multiple Fire Alarm threshold settings for specified pipe networks l Fire Alarm and Pre Alarm outputs l One pipe inlet that can be split into two pipes l Option for inverted mounting l High efficiency aspirator l Air flow monitoring l Easy cable termination l Programmable general purpose input l Configuration and maintenance via Xtralis VS...

Страница 11: ...t always possible particularly on the designs using capillary sampling For these more than two drills sizes are often needed on a particular design to accommodate the flexibility given for the length of capillary pipes being from 0 25m to 4m long Note capillaries should be equal lengths for a particular detector Fire Alarm Threshold Settings There are 4 sensitivity thresholds provided on the XCC d...

Страница 12: ...l 2 5mm all 2 3mm Single Pipe 40 n a all 3 5mm all 3 5mm all 3 5mm all 3 5mm all 3mm all 3mm all 3mm all 3mm all 2 5mm Fire Alarm Threshold Setting n a IV IV III II II I I I I Table 2 2 Pre engineered pipe networks for XCC 010 with drilled holes single branch Pipe Style Branch Length Number of Holes Branch 3 4 5 6 Single Branch 40 50 n a n a all 4mm all 3 5mm Single Branch 30 40 n a all 4mm all 4m...

Страница 13: ...all 3 5mm all 3mm all 3 5mm all 3 5mm all 3 5mm all 3 5mm 1 6 3mm 7 10 3 5mm 1 6 3mm 7 11 3 5mm 1 4 3mm 5 12 3 5mm Fire Alarm Threshold Setting n a IV IV III II II I I I I Table 2 4 Pre engineered pipe networks for XCC 010 with capillaries single branch Pipe Style Branch Length Number of Capillaries Branch 3 4 5 6 Single Branch 40 50 n a n a all 4mm 2x 1 2 3 5mm 3 6 4mm Single Branch 30 40 n a all...

Страница 14: ...XCC Product Guide Xtralis Pty Ltd 8 www xtralis com This page is intentionally left blank ...

Страница 15: ...elays designated Fault Pre Alarm and Fire The relays can be used to connect to the fire alarm control panel or to activate external devices The Fire Alarm and Pre Alarm relay states are non energized and the Fault relay set to energized on power up de energized on Fault 3 3 Relay settings and conditions to change states Table 3 1 Default relay settings and conditions to change state Relay Relay Co...

Страница 16: ...ice The Bias Reset GPI and LED terminals are located on the termination card Figure 3 1 The LED terminals provide a 5V 15 mA DC supply via an internal 220 ohm resistor to power a remote LED Legend Pins A Switch 1 Bias B LED 2 Reset 3 Reset Switch 4 Bias Disable Close Position 5 LED Reset Open Position 6 LED Figure 3 2 Wire connection for Auxiliary GPI Terminals Table 3 2 GPI Functions Function Sta...

Страница 17: ... A Fire Relay EOL Quiescent B Pre Alarm Relay Short Fire Alarm C Fault Relay Open Fault D GPI Input E Conventional Loop Input F Reset Contact G To next detector or EOL resistor Figure 3 3 Typical wiring to a fire panel with EOL resistor 3 7 Wiring to an Addressable Loop Module This wiring example is for wiring XCC detectors to a typical Input Output Loop module 3 input 1 output These are example d...

Страница 18: ...reverse polarity protection to minimize the risk of reverse power connection to the detector Note The XCC detector will not operate when the power supply is reversed Note Operating the detector outside the DC supply voltage range of 18VDC and 30VDC may cause damage to the device Legend A Power Terminal B From 24V Power Supply C Power D Power E 24V Power to Next Device Pins 7 9 GND 8 10 24V Figure ...

Страница 19: ... Secure the mounting bracket to the surface using appropriate fasteners ensuring that the bracket is horizontally straight and sits flush on the surface Determine the ports for cable entry Press out the tabs for the cable entry air inlet and air exhaust ports 4 1 2 Installing the Detector Determine the orientation for mounting the XCC detector Remove the front cover and if necessary separate it fr...

Страница 20: ... 2 Square off and de burr the end of the sampling air pipe ensuring the pipe is free from debris 3 Insert the pipe into the inlet port ensuring a firm fit DO NOT glue the inlet pipes to the Pipe Inlet Man ifold 4 2 2 Air Exhaust Pipe Unplug the air exhaust port at the bottom of the detector If necessary pipe the exhaust back to the protected area The maximum suggested length for the exhaust pipe i...

Страница 21: ...dby capacity Multiplied by battery factor Normally 1 25 4 4 Startup Note An XCC detector must only be powered up by accredited personnel After installing the XCC detector it is necessary to power up the system The system takes approximately 15 seconds to power up If the system fails to power up check all power wires are secured to its terminals and the polarities of the power wires are correctly t...

Страница 22: ...s 1 Use Xtralis VSC to l Accept factory default configurations l Check that the fire alarm threshold setting is appropriate to the pre engineered design used l Select appropriate air flow threshold setting l Normalize the air flow 2 Functionally test the detector by introducing smoke into the last hole 3 Record and confirm the transport time is less than 90 seconds ...

Страница 23: ... intact in the box Is the detector securely locked onto its mounting bracket Is the sampling air pipe firmly connected to the air inlet port Ensure the pipe is NOT glued Have the power wires been connected to the correct terminals on the detector If required has the end of line resistor been connected Have the alarm signaling wires been terminated to the correct terminals of the detector Has the p...

Страница 24: ...XCC Product Guide Xtralis Pty Ltd 18 www xtralis com This page is intentionally left blank ...

Страница 25: ...ble This LED is illuminated when detector is disabled While it remains disabled the Fault relay is de energized indicating a fault condition and the Pre Alarm and Fire Alarm relays will not activate in the case of an alarm l To Reset the unit press button once l To Disable the unit press and hold button for 3 seconds l To Enable the unit press and hold button for 3 seconds l While Disabled faults ...

Страница 26: ...XCC Product Guide Xtralis Pty Ltd 20 www xtralis com This page is intentionally left blank ...

Страница 27: ... Flow X Clean Sampling Point X Flush Pipe Network X Caution While a XCC detector is disabled it will not report Fire events to the FACP Note Prior to any maintenance or testing l Inform appropriate supervising authority about the risk associated with disabling a detector l Ensure that any ancillary devices dependent on the XCC detector is are disabled before work is begun 6 1 Internal Components L...

Страница 28: ...g the detector 6 2 1 Opening 1 Undo the two screws on front cover 2 Open the front cover and allow cover to hang by the attached plastic strap 6 2 2 Closing 1 Replace the front cover over detector enclosure ensuring the plastic strap and cable loom are not wedged between the cover and enclosure 2 Tighten the two screws ...

Страница 29: ...turned on when the air filter cartridge is being replaced 1 Open the front cover Figure 6 2 2 Locate the air filter cartridge A inside the detector compartment refer to Figure 6 3 3 Undo the recessed Phillips head filter screw B 4 Lift out the air filter cartridge 5 Insert a new air filter cartridge 6 Tighten the filter screw B 7 Connect to a PC with Xtralis VSC software to the programming socket ...

Страница 30: ...the aspirator out Legend A Terminal Card C Aspirator Air Hose E Pipe Network Port B Aspirator Wire Loom D Aspirator F Interface Card Slot Figure 6 4 Replacing the Aspirator 6 4 1 Assembly 1 Put the aspirator pipe inlet into the hole leading to the pipe network E 2 Tighten the screws securing the aspirator D 3 Connect the air hose to the aspirator pipe C Ensure a tight fit over the pipe 4 Insert th...

Страница 31: ...ng Operating Conditions XCC 01000 MRN Tested to 25 C to 70 C 13 F to 158 F Recommended Detector Ambient 0 to 39 C 2 F to 103 F Sampled Air 20 to 60 C 4 to 140 F Humidity 10 95 RH non condensing Sampling Pipe Network Maximum Area of Coverage 800m 8000 sq ft Maximum Single Pipe Length 80m max 12 holes Maximum Branched 2 Pipe Lengths 50m each max 6 holes Pipe Design Pre engineered Pipe Networks refer...

Страница 32: ...XCC Product Guide Xtralis Pty Ltd 26 www xtralis com 7 2 Dimensions Figure 7 1 Dimensions of the XCC detector in mm in ...

Страница 33: ...Xtralis Pty Ltd XCC Product Guide www xtralis com 27 Figure 7 2 XCC detector dimensions rear view ...

Страница 34: ...econds Adm Air flow Thresholds Normal Normal Wide Faults Latched Latched n a n a Adm Filter Service Interval 1825 days 5 years 1 day Dependent on environment 1825 days 5 years Adm 7 4 Spare Parts On larger sites having multiple detectors it is advisable to stock certain critical spare parts A list of spare parts with quantities required is given below Table 7 3 Recommended spare parts stock Part N...

Страница 35: ...15 23 Capillary 5 7 Check pipe flow 21 pipe network 14 21 Clean sampling point 21 Commissioning 15 17 Configuration 3 4 9 10 16 Current 25 D Defaults 16 Dimensions 25 26 Disable 10 19 E EN54 20 iii 3 5 end cap 6 7 EOL 11 Exhaust 13 14 17 External Devices 9 F FACP 9 11 Fault 9 15 19 23 24 28 Features 3 4 Filter Cartridge 23 28 inspection 21 screw 21 Service Interval 28 Fire 3 9 19 Fire Alarm 4 9 16...

Страница 36: ...Polarity 12 Power 9 10 12 15 24 Power Supply 9 10 12 15 21 Pre Alarm 4 9 19 Preliminary System Check 16 Programming Socket 9 11 R Relay Terminals 9 Relays 9 19 25 Replacing the Aspirator 24 Reset 9 10 15 19 Reset Filter Settings 23 RS232 11 S Sensitivity 3 28 Serial Number 21 Service 21 28 Simultaneous Alarm Delays 28 Spare Parts 28 Standby 10 15 19 Startup 15 System Isolation 9 T Termination Card...

Отзывы: