background image

 

 

www.xtralis.com 

 

 

UK and Europe

 +44 1442 242 330

 

D-A-CH

 +49 431 23284 1

 

The Americas

 +1 781 740 2223

 

Middle East

 +962 6 588 5622

 

Asia

 +86 21 5240 0077

 

Australia and New Zealand

 +61 3 9936 7000 

The contents of this document are provided on an “as is” basis. No representation or warranty (either express or implied) is made as to the 
completeness, accuracy or reliability of the contents of this document. The manufacturer reserves the right to change designs or specifications 
without obligation and without further notice. Except as otherwise provided, all warranties, express or implied, including without limitation any implied 
warranties of merchantability and fitness for a particular purpose are expressly excluded. 
 
Xtralis, the Xtralis logo, The Sooner You Know, VESDA-E, VESDA, ICAM, ECO, OSID, HeiTel, ADPRO, IntrusionTrace, LoiterTrace, ClientTrace, 
SmokeTrace, XOa, XOh, iTrace, iCommand, iRespond, iCommission,  iPIR, and FMST are trademarks and/or registered trademarks of Xtralis and/or 
its subsidiaries in the United States and/or other countries. Other brand names mentioned herein are for identification purposes only and may be 
trademarks of their respective holder(s). Your use of this document does not constitute or create a licence or any other right to use the name and/or 
trademark and/or label.   
 
This document is subject to copyright owned by Xtralis. You agree not to copy, communicate to the public, adapt, distribute, transfer, sell, modify or 
publish any contents of this document without the express prior written consent of Xtralis. 

 
Doc  09849_02 

 

Replacing the VESDA VLF Filter Cartridge 

To replace the filter cartridge, follow these steps: 

1.  Push in the security tab and lift up the field service access door (A). 

1.  Set the detector to 'Standby' mode by pressing the Disable button for 6 seconds. The Disabled LED 

begins to flash rapidly. After releasing the Disable button the disabled LED will flash more slowly. 

2.  Undo the recessed retaining screw (C) and pull out the old filter (B). 

 

Field service access 
door 

Air filter cartridge 

Retaining screw 

Filter switch 

 

 

3.  Using your finger, firmly press the filter switch (D), in the filter recess of the detector, 5 times within 5 

seconds to indicate to the detector that a new filter is about to be installed (see inset). A LED next to the 
serial interface will flash each time you push the filter switch, and will continue flashing once you have 
successfully pressed the switch 5 times in 5 seconds. 

4.  Insert the new filter (P/N: VSP-005) and tighten the retaining screw. 

5.  Press the Disable button for 6 seconds to return the detector to normal operating mode. 

6.  Record the filter replacement date on the filter. 