Specifications

Supply Voltage:  

18–30 VDC

Power Consumption @ 24 VDC: 

No Display or Programmer

Detector Termination Card

Detector Mounting Box

  

                 Aspirator @ 3000 rpm       Aspirator @ 4200 rpm

 

Quiescent 

With Alarm 

Quiescent  With Alarm

Power 

5.8 W 

6.96 W 

8.16 W 

9.36 W 

Current 

240 mA 

290 mA 

340 mA 

390 mA

Dimensions (WHD):

13.8 in x 8.9 in x 4.9 in (350 mm x 225 mm x 125 mm)

Weight:

9 lbs (4.0 kg) including Display and Programmer modules

IP Rating:  

IP30

Operating Conditions:

Tested to: 14°–131°F (-10°C–55°C)
Detector Ambient: 32°–103°F (0°C–39°C) (Recommended) 
Sampled Air: -4°–140°F (-20°–60°C) 
Humidity: 10%–95% RH, non-condensing 

Please consult your Xtralis office for operation outside 

these parameters or where sampled air is continually 

above 0.015% obs/ft (0.05% obs/m) under normal 

operating conditions.

Sampling Network:

Aggregate pipe length: 650 ft (200 m) 
Maximum Single Length: 325 ft (100 m) 
Pipe Modelling Design Tool: ASPIRE2™

Pipe Size:

External Diameter 1 in (25 mm) 
Internal Diameter 

9

/

16

 in–

7

/

8

 in (15–21 mm)

Programmable Relays:

7 Relays, Contacts rated 2 A @ 30 VDC NO/NC Contacts

Cable Access:

8 x 1 in (25 mm) knockouts in various positions

Cable Termination:

Screw terminals 30–12 AWG (0.2–2.5 sq mm)

Alarm Sensitivity Range: 

0.0015%–6.25% obs/ft (0.005%–20% obs/m)

Alarm Threshold Setting Range:

Alert: 

0.0015%–0.6218% obs/ft (0.005%–1.990% obs/m)  

Action:

 0.0031%–0.6234% obs/ft (0.010%–1.995% obs/m)  

Fire 1: 0.0046%–0.625% obs/ft (0.015%–2.00% obs/m) 
Fire 2: 0.0062%–6.25% obs/ft (0.020%–20.00% obs/m)* 

*Limited to 4% obs/ft (12% obs/m) in UL mode

Event Log:

Up to 18,000 events stored on FIFO basis. 

AutoLearn:

Minimum 15 minutes, maximum 15 days. Recommended 
minimum period 1 day. During AutoLearn thresholds are 
NOT changed from pre-set values.

Software Features:

Referencing: Compensation for external ambient 
conditions.
Four Alarm Levels: Alert, Action, Fire 1 & Fire 2. 
Two Fault Warning Levels: Maintenance and Major fault. 
Software Programmable Relays: 7. 
Maintenance Aids: Filter & Flow monitoring. 
Event reporting via VESDAnet or Event Log. 

Ordering Information

Xtralis VESDA VLP 

VLP-0XX XX (see below) 

 

Remote Programmer 

VRT-100 

Recessed Mounting Kit (Optional) 

VSP-011 

Hand-held Programmer 

VHH-1000 

19 in Sub Rack Configuration 

contact Xtralis

Dimensions

in

mm

A

13.8

350

B

8.9

225

C

2.75

70

D

2.25

57

E

1.37

35

F

1.75

44.5

G

0.87

22.0

H

5.56

14.1

I

0.62

15.9

J

1.31

33.3

K

1.33

34

L

0.94

23.8

M

2

51

N

0.83

21

O

5.56

141

P

1

25.4

Q

0.44

11.1

R

0.37

9.5

S

1.12

28.5

T

1.19

30.2

U 0.125

3.2

Doc. no. 11641_10

The contents of this document are provided on an “as is” basis. No representation or warranty (either express or implied) is made as to the  

completeness, accuracy or reliability of the contents of this document. The manufacturer reserves the right to change designs or specifications 

 

without obligation and without further notice. Except as otherwise provided, all warranties, express or implied, including without limitation any  

implied warranties of merchantability and fitness for a particular purpose are expressly excluded.

This document includes registered and unregistered trademarks. All trademarks displayed are the trademarks of their respective owners.  
Your use of this document does not constitute or create a licence or any other right to use the name and/or trademark and/or label.
This document is subject to copyright owned by Xtralis AG (“Xtralis”). You agree not to copy, communicate to the public, adapt, distribute, transfer,  
sell, modify or publish any contents of this document without the express prior written consent of Xtralis.  

www.xtralis.com

The Americas 

+1 781 740 2223

  Asia 

+852 2297 2438

  Australia and New Zealand

 +61 3 9936 7000

 

Continental Europe

 +41 55 285 99 99

  UK and the Middle East 

+44 1442 242 330

Part: 18253

Xtralis

 

VLP

®

 

VLP-0XX XX

0=Blank Plate

1=Programmer

2=Display

4=Scanner Display

0=Standard Detector Orientation

1=Inverted Detector Orientation

0=Standard Product

1=Custom (consult factory)

Detector Configurations