Product Guide Addendum
VESDA ECO-EX Detector by Xtralis
6
Mechanical Installation
17937_05
Mechanical Installation
Before installing the ECO-EX product, refer to the related conditions of
use for the appropriate certification as indicated in the previous pages of
this document. Failure to adhere to these conditions of use will invalidate
the certification of the product and could potentially render it unsafe for
use in hazardous areas.
Do not install your ECO detector if there are any signs of shipping damage. Inform
your distributor if there is any damage visible.
It is recommended that the installer thoroughly reads all of the installation
instructions before beginning the installation of the VESDA ECO-EX. To install the
VESDA ECO-EX follow the instructions listed below.
Refer to the principle VESDA ECO Product Guide for guidance on the
selection of the optimal location for the product in the aspiration network.
Bear in mind that the ECO-EX requires a secure flat surface for correct
mounting.
With the required location determined, firmly fix the ECO-EX mounting
plate (indicate
d as “C” in Figure 1 on page 3) to the secure flat surface
using the two mounting lugs provided.
Fit the VESDA ECO detector to the mounting plate by location of the pipe
entry points of the detector into the circular brackets at each end of the
mounting plate.
Ensure that the VESDA ECO is upright before and during fitting of the
pipes and electrical connections to ensure that the Guard will fit over it
correctly when the installation is completed.
Refer to the principle VESDA ECO Product Guide for instructions for fitting
the aspirating pipe connections to the ECO-EX.
Perform the necessary Electrical Installation as indicated in the section on
page 8 of this document,
DO NOT
apply power before the guard is fitted
unless otherwise authorized by the site safety authority.
Securely fit the Guard to the mounting plate using the four screws provided
(see Figure 1). Ensure that the guard is oriented correctly such that the
flow direction arrow and status indicators are visible.
Using the Modbus interface, complete the list of installation setup and
configuration items as listed in the Installation section of the VESDA ECO
Product Guide.
Note.
The USB port on the ECO is not accessible while
the Guard is fitted. However some of the initial setup operations can be
undertaken using the USB port in a safe area if this is practical.
Содержание VESDA ECO-EX
Страница 2: ......
Страница 10: ...Product Guide Addendum VESDA ECO EX Detector by Xtralis viii 17937_05 ...
Страница 22: ...Product Guide Addendum VESDA ECO EX Detector by Xtralis 12 Product Specification 17937_05 ...
Страница 23: ...VESDA ECO EX Detector by Xtralis Product Guide Addendum 17937_05 Product Specification 13 ...