AutoLearn Flow
AutoLearn Flow process is initiated within Xtralis VSC or the AutoConfig button located on the main board of
the detector.
During the AutoLearn Flow process, the detector normalizes the airflow and then monitors over time the
average, maximum and minimum air flow levels and sets suitable air flow thresholds that will not give rise to
nuisance flow faults due to normal flow variations.
During the learning cycle, if a flow fault is reached, AutoLearn will not complete its cycle. In this situation the
user must restart the AutoLearn process. If AutoLearn is halted, the flow thresholds will be left at the previous
settings.
Conditions experienced during learning are assumed to be representative of normal operating conditions.
The AutoLearn Flow learning times can be set between 15 minutes and 16 days, with the default being set to
14 days.
6.3
Commissioning Smoke Test
It is recommended that a smoke test be carried out to verify the integrity of the pipe network, to demonstrate
that the system is working and to measure the transport time to the detector.
This test involves introducing a smoke sample at the furthest sampling hole on each pipe and then measuring
the time taken for the smoke to travel to the detector. Results are logged and compared to subsequent tests to
note variations of the system.
Refer to the VESDA Commissioning Guide (document # 10195) for details of the commissioning smoke test.
Содержание VESDA-E VES-A10-P
Страница 1: ...VESDA E VES A10 P Product Guide VES A10 P 4 Pipes August 2019 Document 33794_02 Part Number 30915 ...
Страница 2: ......
Страница 10: ...VESDA E VES A10 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Страница 22: ...VESDA E VES A10 P Product Guide 16 www xtralis com This page is intentionally left blank ...
Страница 52: ...VESDA E VES A10 P Product Guide 46 www xtralis com This page is intentionally left blank ...
Страница 82: ...VESDA E VES A10 P Product Guide 76 www xtralis com This page is intentionally left blank ...
Страница 86: ...VESDA E VES A10 P Product Guide 80 www xtralis com This page is intentionally left blank ...
Страница 103: ...VESDA E VES A10 P Product Guide www xtralis com 97 Figure 7 21 Undo Sampling Module screws ...
Страница 108: ...VESDA E VES A10 P Product Guide 102 www xtralis com ...
Страница 110: ...VESDA E VES A10 P Product Guide 104 www xtralis com This page is intentionally left blank ...
Страница 114: ...VESDA E VES A10 P Product Guide 108 www xtralis com This page is intentionally left blank ...
Страница 120: ...VESDA E VES A10 P Product Guide 114 www xtralis com This page is intentionally left blank ...
Страница 126: ...VESDA E VES A10 P Product Guide 120 www xtralis com Z zone 57 58 81 115 ...